YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
125
Code
Name
Causes
Possible Solutions
These commands are set in Digital Inputs (
H1-xx
,
F3-
10 to F3-25
, and
H7-01 to H7-04
) at the same time:
•
Setting values
61 [Speed Search from Fmax]
and
62 [Speed Search from Fref]
•
Setting values
65, 66, 7A, 7B [KEB Ride-Thru 1 or
2 Activate]
and
68 [High Slip Braking (HSB)
Activate]
•
Setting values
16 [Motor 2 Selection]
and
1A
[Accel/Decel Time Selection 2]
•
Setting values
65, 66 [KEB Ride-Thru 1 Activate]
and
7A, 7B [KEB Ride-Thru 2 Activate]
•
Setting values
40, 41 [Forward RUN (2-Wire),
Reverse RUN (2-Wire)]
and
42, 43 [Run
Command (2-Wire Sequence 2), FWD/REV (2-
Wire Sequence 2)]
•
Setting values
60 [DC Injection Braking
Command]
and
6A [Drive Enable]
•
Setting values
16 [Motor 2 Selection]
and
75, 76
[Up 2 Command, Down 2 Command]
Remove the function settings that are not in use.
Settings for N.C. and N.O. input
[H1-xx]
for these
functions were selected at the same time:
•
Setting value
15 [Fast Stop (N.O.)]
•
Setting value
17 [Fast Stop (N.C.)]
Remove one of the function settings.
These settings were entered while
H1-xx = 2
[External Reference 1/2 Selection]
:
•
b1-15 = 4 [Frequency Reference Selection 2 =
Pulse Train Input]
•
H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠
Frequency Reference]
Set
H6-01 = 0
.
These settings were entered while
H1-xx = 2
[External Reference 1/2 Selection]
:
•
b1-15 = 3 [Option PCB]
or
b1-16 = 3 [Run
Command Selection 2 = Option PCB]
•
No option card is connected to the drive.
Connect an input option card to the drive.
These settings were entered while
H1-xx = 2
[External Reference 1/2 Selection]
:
•
b1-15 = 1 [Analog Input]
•
H3-02 ≠ 0 [Terminal A1 Function Selection ≠
Frequency Reference]
or
H3-10 ≠ 0 [Terminal A2
Function Selection ≠ Frequency Reference]
Set
H3-02 = 0
or
H3-10 = 0
.
These parameters are set at the same time:
•
H1-xx ≠ 6A [Drive Enable]
•
H2-xx = 38 [Drive Enabled]
Correct the parameter settings.
These parameters are set at the same time:
•
H6-01 ≠ 3 [PG Speed Feedback (V/F Control)]
•
H1-xx = 7E [Reverse Rotation Identifier]
Correct the parameter settings.
These parameters are set at the same time:
•
H1-xx = 75/76 [Up 2 /Down 2 Command]
•
H3-01, H3-05, H3-09 = 1 [Terminal A1, A2, A3
Signal Level Select = -10 to +10V (Bipolar
Reference)]
Remove one of the function settings.
These parameters are set at the same time:
•
H1-xx = 62 [Speed Search from Fref]
•
H5-22 = 1 [Speed Search from MODBUS =
Enabled]
Remove one of the function settings.
These settings do not agree:
•
A PG-RT3 option is connected to the drive.
•
H1-xx = 16 [Motor 2 Selection]
is set.
Correct the parameter settings.
Note:
The Motor Switch function is not available with the PG-RT3
option.
Code
Name
Causes
Possible Solutions
oPE05
Run Cmd/Freq Ref Source Sel Err
The setting to assign the Run command or frequency
reference to an option card or the pulse train input is
incorrect.
Correct the parameter settings.
b1-01 = 3 [Frequency Reference Selection 1 =
Option PCB]
is set, but there is no option card
connected to the drive.
b1-02 = 3 [Run Command Selection 1 = Option
PCB]
is set, but there is no option card connected to
the drive.
Connect an option card to the drive.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...