450
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
T1-06: Number of Motor Poles
No.
(Hex.)
Name
Description
Default
(Range)
T1-06
(0706)
Number of Motor Poles
Sets the number of motor poles.
4
(2 to 120)
■
T1-07: Motor Base Speed
No.
(Hex.)
Name
Description
Default
(Range)
T1-07
(0707)
Motor Base Speed
Sets the motor base speed for Auto-Tuning (min
-1
(r/min)).
1750 min
-1
(r/min)
(0 - 35400 min
-1
(r/min))
■
T1-09: Motor No-Load Current
No.
(Hex.)
Name
Description
Default
(Range)
T1-09
(0709)
Motor No-Load Current
Sets the no-load current of the motor.
-
(0A - T1-04; max. of 2999.9)
Note:
The display units are different for different models:
•
0.01 A: B001 - B018, 2001 - 2042, 4001 - 4023
•
0.1 A: 2056 - 2082, 4031 - 4060
The value shown is the no-load current that the drive automatically calculates from the values set in
T1-02 [Motor
Rated Power]
and
T1-04 [Motor Rated Current]
. Set the no-load current shown on the motor test report. If the motor
test report is not available, do not change this parameter.
■
T1-10: Motor Rated Slip Frequency
No.
(Hex.)
Name
Description
Default
(Range)
T1-10
(070A)
Motor Rated Slip Frequency
Sets motor rated slip.
-
(0.000 - 20.000 Hz)
Shows 0.000 Hz as the default value. Set the rated slip shown on the motor test report. If the motor test report is not
available, do not change this parameter.
■
T1-11: Motor Iron Loss
No.
(Hex.)
Name
Description
Default
(Range)
T1-11
(070B)
Motor Iron Loss
Sets the iron loss for calculating the energy-saving coefficient.
Determined by E2-11 or E4-
11
(0 - 65535 W)
Note:
The default setting is different for different motor codes and motor parameter settings.
The value shown is the
E2-10 [Motor Iron Loss]
or
E4-10 [Motor 2 Iron Loss]
for the motor output set in
T1-02
[Motor Rated Power]
. If the motor test report is available, enter the motor iron loss value to
T1-11
.
■
T1-12: Test Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
T1-12
(0BDB)
Test Mode Selection
Sets the function to enable Test Mode after Stationary Auto-Tuning. When you can operate the motor
with a light load attached after Stationary Auto-Tuning is complete, enable this parameter.
0
(0, 1)
0 : No
1 : Yes
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...