358
YASKAWA
TOEPYAIGA5002A GA500 Programming
Figure 2.104 Connect Motor to PTC Thermistor Input
2. Set drive DIP switch S1-3 to V (voltage).
3. Set these MFAI terminals:
•
H3-09 = 0 [Terminal A2 Signal Level Select = 0-10V (LowLim=0)]
.
•
H3-10 = E [Terminal A2 Function Selection = Motor Temperature (PTC input)]
.
4. Set these
L1 parameters
:
•
L1-03 [Motor Thermistor oH Alarm Select]
•
L1-04 [Motor Thermistor oH Fault Select]
•
L1-05 [Motor Thermistor Filter Time]
■
L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name
Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
Determined by A1-02
(0 - 6)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
•
Output Current
•
Output Frequency
•
Motor thermal characteristics
•
Time characteristics
If the drive detects motor overload, the drive will trigger an
oL1 [Motor Overload]
and stop the drive output.
Set
H2-01 = 1F [Term MA/MB-MC Function Selection = Motor Overload Alarm (oL1)]
to set a motor overload
alarm. If the motor overload level is more than 90% of the
oL1
detection level, the output terminal activates and
triggers an overload alarm.
0 : Disabled
Disable motor protection when motor overload protection is not necessary or when the drive is operating more than
one motor.
Refer to
for an example of the circuit configuration to connect more than one motor to one drive.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...