2.8 H: Terminal Function Selection
292
YASKAWA
TOEPYAIGA5002A GA500 Programming
Note:
•
To input the Run command, activate the terminal for 1 ms minimum.
•
The default setting for
b1-17 [Run Command at Power Up]
is
0 [Disregard existing RUN command]
. If you enable the Run command on an
energized drive, the protective function activates and the
flashes quickly. When the application will let an energized drive Run, set
b1-17 = 1 [Accept Existing RUN Command]
.
■
1: LOCAL/REMOTE Selection
Setting Value
Function
Description
1
LOCAL/REMOTE Selection
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
Note:
•
When the MFDI terminal sets the LOCAL/REMOTE selection,
on the keypad is disabled.
•
When LOCAL Mode is selected, the green light for
comes on.
•
When the Run command is ON, you cannot switch between LOCAL Mode and REMOTE Mode.
ON : LOCAL
The keypad is the Frequency reference source and Run command source.
OFF : REMOTE
The frequency reference and Run command settings are set in
b1-01
,
b1-02 [Frequency Reference Selection 1/2]
or
b1-15
,
b1-16 [Run Command Selection 1/2]
.
■
2: External Reference 1/2 Selection
Setting Value
Function
Description
2
External Reference 1/2
Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
Note:
When the drive is receiving a Run command, you cannot switch between reference sources.
ON :
b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF :
b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
■
3: Multi-Step Speed Reference 1
Setting Value
Function
Description
3
Multi-Step Speed Reference
1
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
4: Multi-Step Speed Reference 2
Setting Value
Function
Description
4
Multi-Step Speed Reference
2
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
5: Multi-Step Speed Reference 3
Setting Value
Function
Description
5
Multi-Step Speed Reference
3
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...