178
YASKAWA
TOEPYAIGA5002A GA500 Programming
■
b3-25: Speed Search Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-25
(01C8)
Expert
Speed Search Wait Time
Sets the length of time the drive will wait to start the Speed Search Retry function.
0.5 s
(0.0 - 30.0 s)
If the drive detects these faults during speed search, increase the setting value:
•
oC [Overcurrent]
•
ov [Overvoltage]
•
SEr [Speed Search Retries Exceeded]
■
b3-26: Direction Determination Level
No.
(Hex.)
Name
Description
Default
(Range)
b3-26
(01C7)
Expert
Direction Determination
Level
Sets the level to find the motor rotation direction. Increase the value if the drive cannot find the
direction.
1000
(40 to 60000)
■
b3-29: Speed Search Back-EMF Threshold
No.
(Hex.)
Name
Description
Default
(Range)
b3-29
(077C)
Expert
Speed Search Back-EMF
Threshold
Sets the induced voltage for motors that use Speed Search. The drive will start Speed Search when
the motor induced voltage level is the same as the setting value. Usually it is not necessary to change
this setting.
10%
(0 - 10%)
To make adjustments, gradually decrease the setting value. If you decrease the setting value too much, speed search
will not operate correctly.
■
b3-31: Spd Search Current Reference Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b3-31
(0BC0)
Expert
Spd Search Current
Reference Lvl
Sets the current level that decreases the output current during Current Detection Speed Search.
1.50
(1.50 - 3.50)
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
Note:
The setting is a ratio with respect to
E9-06 [Motor Rated Current (FLA)]
× 0.5 when
A1-02 = 8 [Control Method Selection = EZOLV]
.
■
b3-32: Spd Search Current Complete Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b3-32
(0BC1)
Expert
Spd Search Current
Complete Lvl
Sets the current level that completes Speed Search.
1.20
(0.00 - 1.49)
The Current Detection Speed Search gradually decreases the output frequency to search for the motor speed when the
output current is equal to or less than Speed Search Current Complete Level.
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
Note:
The setting is a ratio with respect to
E9-06 [Motor Rated Current (FLA)]
× 0.5 when
A1-02 = 8 [Control Method Selection = EZOLV]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...