Digital Operator Constants: o
The following settings are made with the Digital Operator constants (o constants): Monitor select and multi-
function selections.
Monitor Select: o1
User constants for Digital Operator Displays are shown in the following table.
Multi-function Selections: o2
User constants for Digital Operator key functions are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
o1-05
LCD brightness
adjustment
Set a smaller value to lighten
the LCD and a larger value to
darken the LCD (standard:
10).
0 to 20
10
No
A
A
6E4H
LCD Contrast
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
o2-01
LOCAL/REMOTE
key enable/disable
Sets the Digital Operator Local/
Remote Key
0: Disabled
1: Enabled (Switches between the
Digital Operator and the
constant settings.)
0 or 1
1
No
A
A
6F0H
Local/Remote Key
o2-02
STOP key during
control circuit ter-
minal operation
Sets the Stop Key in the run mode.
0: Disabled (When the Run Com-
mand is issued from and
external terminal, the Stop Key
is disabled.)
1: Enabled (Effective even during
run.)
0 or 1
0
No
A
A
6F1H
Oper STOP Key
o2-04
kVA selection
Not initialized in A1-03 (Initialize).
Code: rated voltage, kVA, kW,
rated current
60: 3300V, 200 kVA, 132 kW, 35 A
61: 3300V, 285 kVA, 200 kW, 50 A
62: 3300V, 400 kVA, 315 kW, 70 A
63: 3300V, 570 kVA, 450 kW, 100 A
64: 3300V, 800 kVA, 630 kW, 140 A
65: 3300V, 1150 kVA, 900 kW, 200 A
66: 3300V, 1500 kVA, 1250 kW, 260 A
67: 3300V, 2300 kVA, 1800 kW, 400 A
68: 3300V, 3000 kVA, 2500 kW, 520 A
70: 6600V, 400 kVA,
250 kW, 35 A
71: 6600V, 570 kVA,
400 kW, 50 A
72: 6600V, 800 kVA,
630 kW, 70 A
73: 6600V, 1150 kVA, 900 kW, 100 A
74: 6600V, 1600 kVA, 1250 kW, 140 A
75: 6600V, 2300 kVA, 1800 kW, 200 A
76: 6600V, 3000 kVA, 2500 kW, 260 A
77: 6600V, 4600 kVA, 3550 kW, 400 A
78: 6600V, 6000 kVA, 5000 kW, 520 A
Usually setting is not necessary.
60 to
FFH
Code
corre-
spond-
ing to
Inverter
capacity
No
A
A
6F3H
kVA selection