2.2 Mechanical Installation
42
YASKAWA ELECTRIC
EZZ010926 FSDrive-MV1000 Instructions
◆
Checking the Installation Space
Secure the space indicated below around the drive to maintain sufficient cooling.
Note:
If the installation space for the drive is restricted and the space indicated below cannot be secured, contact your Yaskawa
representatives or the nearest Yaskawa sales office.
Figure 2.1
Figure 2.1 Drive Installation Space
Table 2.2 Precautions on Installation Space
A – Min. 1000 mm
D – Min. 600 mm
B – Min. 30 mm
E – Max. 800 mm
C – Min. 2000 mm
Installation
Space
Details
A (Top)
Sufficient space to remove the cooling fans from the top of the drive is required for fan replacement. Air is expelled
through the cooling fans on top of the drive. If the cooling fans are too close to the ceiling, the air that has been expelled
may be drawn back into the drive, reducing the cooling performance.
B (Sides)
–
C (Front)
Sufficient space is required to allow Power Cells to be drawn out and placed on the lifter used to convey them when
Power Cells need to be replaced.
D (Rear)
Sufficient working space is required to route the cables and to install anchors on the back of the drive.
B
C
D
E
A
B
Front views
Side view
Door opening dimension
Door opening dimension
Front
Rear