5.6 Operator Programming Error
172
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
Digital Operator Display
Error Name
oPE07
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and
PID functions conflict.
Cause
Possible Solutions
At least two analog input terminals are set to the same
function (i.e., at least two of these parameters has the
same setting: H3-02 and H3-10).
Change the settings to H3-02 and H3-10 so that functions no longer conflict.
Note:
Both 0 (frequency reference bias) and F (not used) or 1F (Through mode) can be
set to H3-02 and H3-10 simultaneously.
The following simultaneous contradictory settings:
H3-02 and H3-10 = C (PID Target Value) while b5-18 = 1
(enables b5-19 as the target PID value)
Disable one of the PID selections.
Digital Operator Display
Error Name
oPE08
Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.
Cause
Possible Solutions
Attempted to use a function that is not valid for the
selected control mode.
Check the motor control method and the functions available.
In Open Loop Vector Control, n2-02 is greater than n2-03. Correct parameter settings so that n2-02 is less than n2-03.
In Open Loop Vector Control, C4-02 is greater than
C4-06.
Correct parameter settings so that C4-02 is less than C4-06.
Note:
Use U1-18 to find which parameters are set outside the specified setting range. Other errors are given precedence over oPE08
when multiple errors occur simultaneously.
Digital Operator Display
Error Name
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled
(b5-01 = 1 to 4).
Cause
Possible Solutions
The following simultaneous contradictory settings have
occurred:
• b5-15 not 0.0 (PID Sleep Function Start Level)
• The stopping method is set to either DC Injection
Braking or coast to stop with a timer (b1-03 = 2 or 3).
Set b5-15 to another value other than 0.
Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
When b5-01 = 1 or 2 (PID output 1/2), d2-02 (Frequency
Reference Lower Limit)
≠
0 was specified.
Correct the parameter settings.
When b5-01 = 1 or 2 (PID output 1/2), b5-11 (PID Output
Reverse Selection) = 1 (Rotation direction reverses with
negative PID output) was specified.
Correct the parameter settings.
PID control is set to b5-01 = 3 or 4, but the lower limit for
the frequency reference (d2-01) is not 0.
Correct the parameter settings.
Digital Operator Display
Error Name
oPE10
V/f Data Setting Error
One of the following setting errors have occurred:
• E1-09
≤
E1-07 < E1-06
≤
E1-11
≤
E1-04
• E3-09
≤
E3-07 < E3-06
≤
E3-11
≤
E3-04
Cause
Possible Solutions
V/f Pattern Setting Error
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11. For motor 2, correct
E3-04, E3-06, E3-07, E3-09, and E3-11.
Содержание FSDrive-MV1000 Series
Страница 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 38: ...1 4 Component Names and Configurations 38 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 136: ...4 9 Checking and Saving Parameter Default Values 136 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...