YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
93
Drive Model
GFCI Model
Manufacturer: Mitsubishi Electric
Rated Current
A
Rated Leakage Current
mA
4180
NV400-SW
300
500
4240
NV400-SW
350
500
4302
NV400-SW
400
500
4361
NV630-SW
500
500
4414
NV630-SW
630
500
4477
NV630-SW
630
500
4515
NV800-SEW
800
500
4590
NV800-SEW
800
500
4720
NV800-SEW
800
500
◆
EMC Directive
Drives with built-in EMC filters were tested in accordance with European standard IEC/EN 61800-3, and comply
with the EMC Directive.
■
Install a Drive to Conform to the EMC Directive
Use this procedure to install drives that comply with the EMC Directive when the drive is a single unit or installed in
a larger device.
1.
Install the drive on a grounded metal plate.
2.
Wire the drive and motor.
3.
Ground the wire shielding on the drive side and motor side.
A - Drive
B - 100 m (328 ft) maximum
C - Motor
D - Metal conduit
E - Grounding wire
Figure 13.3 Wiring the Drive and Motor
Note:
• Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
• The maximum wiring length between the drive and motor is 100 m (328 ft). Keep the wire as short as possible.
• Keep the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.