7.3 Trial Operation for the Servomotor without a Load
7.3.1 Preparations
7-7
7
Trial Operation
7.3
Trial Operation for the Servomotor without a Load
You use jog operation for trial operation of the Servomotor without a load.
Jog operation is used to check the operation of the Servomotor without connecting the SERVO-
PACK to the host controller. The Servomotor is moved at the preset jog operation speed.
7.3.1
Preparations
Always check the following before you execute jog operation.
•
The parameters must not be write prohibited.
•
The main circuit power supply must be ON.
•
There must be no alarms.
•
There must be no hard wire base block (HWBB).
•
The servo must be OFF.
•
The jog operation speed must be set considering the operating range of the machine.
The jog operation speed is set with the following parameters.
•
Rotary Servomotors
•
Direct Drive Servomotors
•
Linear Servomotors
CAUTION
During jog operation, the overtravel function is disabled. Consider the range of motion of
your machine when you jog the Servomotor.
Pn304
Jog Operation Speed
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 min
-1
500
Immediately Setup
Pn305
Soft Start Acceleration Time
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 ms
0
Immediately
Setup
Pn306
Soft Start Deceleration Time
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 ms
0
Immediately
Setup
Pn304
Jog Operation Speed
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
0.1 min
-1
500
Immediately Setup
Pn305
Soft Start Acceleration Time
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 ms
0
Immediately
Setup
Pn306
Soft Start Deceleration Time
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 ms
0
Immediately
Setup
Pn383
Jog Operation Speed
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 mm/s
50
Immediately
Setup
Pn305
Soft Start Acceleration Time
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 ms
0
Immediately
Setup
Pn306
Soft Start Deceleration Time
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 ms
0
Immediately
Setup