5.12 Motor Stopping Methods for Servo OFF and Alarms
5.12.2 Servomotor Stopping Method for Alarms
5-38
Stopping the Servomotor by Setting the Deceleration Time
To specify the Servomotor deceleration time and use it to stop the Servomotor, set Pn30A
(Deceleration Time for Servo OFF and Forced Stops).
If you set Pn30A to 0, the Servomotor will be stopped with a zero speed.
The deceleration time that you set in Pn30A is the time to decelerate the Servomotor from the
maximum motor speed.
Pn30A
Deceleration Time for Servo OFF and Forced Stops
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 ms
0
Immediately
Setup
Pn30A
=
Maximum speed
Operating speed
Actual
deceleration time
Actual deceleration time
Operating speed
Maximum speed
× Deceleration time (Pn30A)