B.3 Defaults by Converter Model
B.3 Defaults by Converter Model
The following tables show parameters and default settings that change with o2-04 (drive model selection).
Table B.1 200 V Class Model Default Settings by Converter Model Selection
Table B.2 400 V Class Model Default Settings by Converter Model Selection
No.
Name
Unit
Default Settings
–
Model
–
2A0005 2A0010 2A0020 2A0030 2A0050 2A0065 2A0090 2A0130
o2-04
Model Selection
Hex
68
6B
6E
70
73
75
76
78
d8-01
DC Bus Voltage Reference
V
330
330
330
330
330
330
330
330
L2-02
Momentary Power Loss Ride-Thru Time
s
1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-05
Undervoltage Detection Level (Uv)
V
190
190
190
190
190
190
190
190
L2-21
AUv Detection Level
V
150
150
150
150
150
150
150
150
L8-02
Overheat Alarm Level
°
C
110
125
115
125
130
135
135
130
L8-09
Output Ground Fault Detection Selection
–
1
1
1
1
1
1
1
1
L8-66
Power Supply Fault Detection Voltage Level
%
50
50
50
50
50
50
50
50
C7-47
Adjustment Reactor 1
mH
2.450
1.267 0.645 0.443 0.263 0.184 0.136 0.092
C7-51
Adjustment Reactor 2
mH
0.809
0.418 0.213 0.146 0.087 0.061 0.045 0.030
C6-02
Carrier Frequency Selection
–
3
3
3
3
2
2
2
2
L8-35
Installation Method Selection
–
0
0
0
0
0
0
0
0
No.
Name
Unit
Default Settings
–
Model
–
4A0005 4A0010 4A0020 4A0030 4A0040 4A0060 4A0100 4A0130 4A0185 4A0270 4A0370 4A0630
o2-04 Model Selection Hex
97
9A
9D
9F
A1
A3
A5
A7
A9
AC
AE
B2
d8-01
DC Bus Voltage
Reference
V
660
660
660
660
660
660
660
660
660
660
660
660
L2-02
Momentary Power
Loss Ride-Thru
Time
s
0.5 1.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-05
Undervoltage
Detection Level
(Uv)
V
380
380
380
380
380
380
380
380
380
380
380
380
L2-21
AUv Detection
Level
V
300
300
300
300
300
300
300
300
300
300
300
300
L8-02
Overheat Alarm
Level
°
C
110
115
115
115
115
130
140
145
140
130
130
130
L8-09
Output Ground
Fault Detection
Selection
–
1
1
1
1
1
1
1
1
1
1
1
1
L8-66
Power Supply
Fault Detection
Voltage Level
%
50
50
50
50
50
50
50
50
50
50
50
50
C7-47
Adjustment
Reactor 1
mH
9.189 4.594 2.450 1.710 1.267 0.855 0.507 0.350 0.245 0.179 0.131 0.064
C7-51
Adjustment
Reactor 2
mH
3.308 1.654 0.882 0.615 0.456 0.308 0.183 0.126 0.088 0.065 0.047 0.023
C6-02
Carrier Frequency
Selection
–
3
3
3
3
3
3
2
2
2
1
1
1
L8-35
Installation
Method Selection
–
0
0
0
0
0
0
0
0
0
0
0
0