o4-24: bAT Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-24
(310F)
RUN
bAT Detection Selection
Selects the operation when the drive detects
bAT [Keypad Battery Low Voltage]
and
TiM [Keypad
Time Not Set]
.
0
(0 - 2)
0 : Disable
No detection
1 : Enable (Alarm Detected)
The keypad shows
TiM
or
bAT
, and the drive continues operation. The output terminal set for
Alarm [H2-01 to
H2-05 = 10]
switches ON.
2 : Enable (Fault Detected)
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC will turn ON, and
MB-MC will turn OFF.
◆
o5: Log Function
The data log function saves drive status information as a CSV file in the microSD memory card in the keypad.
Monitors Ux-xx
are the source of data log information. You can record a maximum of 10 monitors.
Change the LCD keypad screen from the main menu to the Diagnostic Tools screen and select the data log
function. Set the number of the monitor to record and the sampling time, then start to record the data log.
Table 11.36 Setting Parameters for Data Log Items
No.
Name
Default
Data Log Monitors
o5-03
Log Monitor Data 1
101
U1-01 [Frequency Reference]
o5-04
Log Monitor Data 2
102
U1-02 [Output Frequency]
o5-05
Log Monitor Data 3
103
U1-03 [Output Current]
o5-06
Log Monitor Data 4
107
U1-07 [DC Bus Voltage]
o5-07
Log Monitor Data 5
108
U1-08 [Output Power]
o5-08
Log Monitor Data 6
000
Not selected
o5-09
Log Monitor Data 7
000
Not selected
o5-10
Log Monitor Data 8
000
Not selected
o5-11
Log Monitor Data 9
000
Not selected
o5-12
Log Monitor Data 10
000
Not selected
Note:
•
Do not de-energize the drive or disconnect the keypad from the drive during log transfer communication. A loss of connection can
cause the log function to fail after you restore power or connect the keypad.
•
You can use a microSDHC card that has a maximum of 32 GB capacity.
■
Log File Specifications
Item
Specification
File storage location
A folder called [Log_File] is created in the root directory of the microSD card.
Filename
GLOG0xxx.csv
Note:
[xxx] identifies a 3-digit decimal number
Maximum number of files
999 (GLOG0001.csv to GLOG0999.csv)
Character code
ASCII code
Line break code
<CR><LF>
Separating character
[ , ] (Commas)
Header rows
First Row: Drive information including the drive model, software version, control method, and sampling time
Second Row: Log data information including the monitor number, number decimal points, and unit code
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...