2 : 0 to 100% (Lower Limit at 0)
■
H7-41: Virtual Analog Output Function
No.
(Hex.)
Name
Description
Default
(Range)
H7-41
(1164)
Virtual Analog Output
Function
Sets the monitor to be output from the virtual analog output.
102
(0 - 999)
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H7-41 = 102
to monitor
U1-02 [Output Frequency]
.
■
H7-42: Virtual Analog Output FilterTime
No.
(Hex.)
Name
Description
Default
(Range)
H7-42
(1165)
Virtual Analog Output
FilterTime
Sets the time constant for a primary filter of the virtual analog output.
0.00 s
(0.00 - 2.00 s)