H3: Analog Inputs
WARNING!
Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are
correct. If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have three analog input terminals, named terminals A1, A2, and A3.
H3 parameters
select the functions set
to these analog input terminals and adjust signal levels.
The table shows the functions that you can set to analog input terminals. Use
H3-02, H3-06, and H3-10 [MFAI
Function Select]
to set functions.
Table 11.32 Multi-Function Analog Input Terminal Settings
Setting Value
Function
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Torque Detection Level
8
Stall Prevent Level during Run
C
Overload Detection Level
Setting Value
Function
D
Frequency Bias
E
Motor Temperature (PTC Input)
F
Not Used
10
Forward Torque Limit
11
Reverse Torque Limit
12
Regenerative Torque Limit
14
Torque Compensation
15
General Torque Limit
1F
Not Used
Note:
All analog input scaling uses gain and bias for adjustment. Set the gain and bias values correctly.
■
Example Analog Input Settings
•
The function set for terminal A1 is set with
Frequency Reference [H3-02 = 0]
, the gain is
200% [H3-03 =
200.0]
, and the bias is
0% [H3-04 = 0.0]
.
When you input a 10 V signal, the frequency reference will be 200%.
When you input a 5 V signal, the frequency reference will be 100%. As the drive output at this time is restricted
by
E1-04 [Maximum Output Frequency]
, the frequency reference will be at 100% when a signal of 5 Vor more
is input.
Figure 11.71 Freq Reference When the Analog Input Gain Setting Is Adjusted
•
The function set for terminal A1 is set with
Frequency Reference [H3-02 = 0]
, the gain is
100% [H3-03 =
100.0]
, and the bias is
-25% [H3-04 = -25.0]
.
When you input a 0 V signal, the frequency reference will be -25%.
When
H3-01 = 0 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0)]
, when you input a 0 V to 2 V
signal, the frequency reference will be 0%. When you input a 2 V to 10 V signal, the frequency reference will
be 0% to 100%.
When
H3-01 = 1 [-10 to +10V (Bipolar Reference)]
, it enables signals of positive and negative polarities. When
you input a 0 V to 2 V signal, and the motor rotates in reverse.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...