YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
709
■
H2-36: Comparator 1 Ineffective Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-36
(159E)
Comparator 1 Ineffective
Time
Sets the length of time that
CP1 [Comparator1 Limit Fault]
is disabled.
0.0 s
(0.0 - 1000.0 s)
Note:
•
After you enter a Run command and wait for the time set in this parameter, the drive will monitor operation and make sure that it is in
the Comparator 1 range until you enter the Stop command.
•
When
CP1
detection is disabled, the drive will activate the output terminal set for
Comparator 1 [H2-xx = 66]
.
■
H2-37: Comparator 2 Ineffective Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-37
(159F)
Comparator 2 Ineffective
Time
Sets the length of time that
CP2 [Comparator2 Limit Fault]
is disabled.
0.0 s
(0.0 - 1000.0 s)
Note:
•
After you enter a Run command and wait for the time set in this parameter, the drive will monitor operation and make sure that it is in
the Comparator 2 range until you enter the Stop command.
•
When
CP2
detection is disabled, the drive will activate the output terminal set for
Comparator 2 [H2-xx = 67]
.
■
H2-40: Mbus Reg 15E0h bit0 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-40
(0B58)
Mbus Reg 15E0h bit0
Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-41: Mbus Reg 15E0h bit1 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-41
(0B59)
Mbus Reg 15E0h bit1
Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-42: Mbus Reg 15E0h bit2 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-42
(0B5A)
Mbus Reg 15E0h bit2
Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-60: Term M1-M2 Secondary Function
No.
(Hex.)
Name
Description
Default
(Range)
H2-60
(1B46)
Expert
Term M1-M2 Secondary
Function
Sets the second function for terminal M1-M2. The logical calculation results of the terminals
assigned to functions by
H2-01 [Term M1-M2 Function Selection]
is output.
F
(0 - FF)
■
H2-61: Terminal M1-M2 Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-61
(1B47)
Expert
Term MA,MB,MC Logical
Operation
Selects the logical operation for the two functions selected by
H2-01 [Term M1-M2 Function
Selection]
and
H2-60 [Term M1-M2 Secondary Function]
.
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 703
for more information about the relationship between parameter
settings and logical operations.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...