SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
–
The lower limit value of the frequency reference is set for both the analog input and
d2-02
–
The lower limit value of the analog input is higher than the setting value of
d2-02
Note:
Refer to
“
d4-10: Up/Down Freq Lower Limit Select
”
for details.
The following time chart shows an example of how Up/Down command operates. In this example, the lower limit
value of the frequency reference is set in
d2-02
. The time chart when
Freq Reference Retention Select [d4-01]
is
enabled and disabled is shown below.
Figure 11.52 Up/Down Command Time Chart
■
11: Down Command
Setting Value
Function
Description
11
Down Command
You must also set Setting
10 [Up Command]
. Sets the command to use a push button switch to decrease the drive frequency
reference
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
Note:
•
If only one of either the Up command or Down command has been set,
oPE03 [Multi-Function Input Setting Err]
will be detected.
•
If two or more of the following functions have been allocated at the same time,
oPE03
occurs.
–
Up/Down command
–
Accel/Decel Ramp Hold
–
Reference Sample Hold
–
Offset Frequency 1, 2, 3 addition
•
The Up/Down command can be used when the keypad is in REMOTE mode or
b1-01 ≠ 0 [Frequency Reference Selection 1 ≠
Keypad]
.
•
The Up/Down command does not function when switching to parameter
b1-15 [Frequency Reference Selection 2]
using
External
Reference 1/2 Selection [H1-xx = 2]
.
If the Up command is input, the frequency reference increases, and if Down command is input, the frequency
reference decreases.
Up and Down command has priority over all other frequency references. When the Up/Down command is
enabled, the following frequency references will be disregarded.
•
Frequency reference from Keypad
[b1-01 = 0]
•
Frequency reference from Analog Input
[b1-01 = 1]
■
12: Forward Jog
Setting Value
Function
Description
12
Forward Jog
Sets the command to operate the motor in the forward direction at the Jog Frequency set in
d1-17 [Jog Reference]
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...