YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
691
Note:
Refer to
Setting Procedures for Multi-step Speed Operation on page 622
for more information.
■
5: Multi-Step Speed Reference 3
Setting Value
Function
Description
5
Multi-Step Speed Reference
3
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
Note:
Refer to
Setting Procedures for Multi-step Speed Operation on page 622
for more information.
■
6: Jog Reference Selection
Setting Value
Function
Description
6
Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in
d1-17
. The JOG Frequency command overrides
Frequency References 1 to 8 (d1-01 to d1-08]
.
■
7: Accel/Decel Time Selection 1
Setting Value
Function
Description
7
Accel/Decel Time Selection
1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/Deceleration Time 2 [C1-03, C1-04]
.
Note:
Refer to
C1: Accel & Decel Time on page 600
for more information.
■
8: Baseblock Command (N.O.)
Setting Value
Function
Description
8
Baseblock Command (N.
O.)
Sets the command that stops drive output and coasts the motor to stop when a baseblock command (N.O.) is input.
The keypad flashes
bb [Baseblock]
. Acceleration always starts from the zero speed when the Run command is
input. The drive keeps the baseblock state when the Run command is not input.
WARNING!
Sudden Movement Hazard. When you use a mechanical holding brake with the drive in a lifting application, you
must close the brake if an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock
command, the motor will suddenly coast and the load will slip, which can cause serious injury or death.
Figure 11.51 Baseblock Command Time Chart
ON : Baseblock (drive output stop)
OFF : Normal operation
■
9: Baseblock Command (N.C.)
Setting Value
Function
Description
9
Baseblock Command (N.
C.)
Sets the command that stops drive output and coasts the motor to stop when baseblock command (N.C.) is input (turned OFF).
The keypad flashes
bb [Baseblock]
.
WARNING!
Sudden Movement Hazard. When you use a mechanical holding brake with the drive in a lifting application, you
must close the brake if an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock
command, the motor will suddenly coast and the load will slip, which can cause serious injury or death.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...