MFDI for DI-A3
When you set to
F3-01 = 8 [Digital Input Function Selection = Multi-Function Digital Input]
, you can use the
digital input option DI-A3 as the multi-function input. To use this as the multi-function input, set such that
b1-01
≠ 3 [Frequency Reference Selection 1 ≠ Option PCB]
.
Select the function for the DI-A3 terminals with
F3-10 to F3-25 [Terminal D0 to DF Function Selection]
.
Note:
•
Refer to
H1-xx
“
MFDI Function Selections
”
for more information about multi-function digital input setting values.
•
You cannot set
20 to 2F [External Fault]
to
F3-10
to
F3-25
.
•
Set
F3-10 to F3-25 = F [Not Used]
when not using the DI-A3 multi-function input. The through mode function is not supported.
•
Terminal Dx of the DI-A3 is read twice in accordance with the setting of
b1-06 [Digital Input Reading]
.
•
If you set
F3-01 = 8
when DI-A3 is the frequency reference source (
b1-01 or b1-15 = 3 [Frequency Reference Selection 1/2 = Option
PCB]
), the drive will detect
oPE05 [Run Cmd/Freq Ref Source Sel Err]
.
•
The following functions can be used together with the DI-A3 multi-function input.
–
H1-40 to H1-42 [Mbus Reg 15C0h bit0 to bit2 Input Func]
–
H7-01 to H7-04 [Virtual Multi-Function Inputs 1 to 4]
■
F3-01: Digital Input Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-01
(0390)
Digital Input Function
Selection
Sets the data format of digital input signals. This parameter is enabled when
o1-03 = 0 or 1
[Frequency Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)]
.
0
(0 - 8)
Note:
When
o1-03 = 2 [min
-1
(r/min) unit]
or
3 [User Units]
, the input signal type is BCD. The
o1-03
value sets the setting units.
0 : BCD, 1% units
1 : BCD, 0.1% units
2 : BCD, 0.01% units
3 : BCD, 1 Hz units
4 : BCD, 0.1 Hz units
5 : BCD, 0.01 Hz units
6 : BCD (5-digit), 0.01 Hz
7 : Binary input
The setting unit and setting range are different for different values of
F3-03 [Digital Input Data Length Select]
.
•
F3-03 = 0 [8-bit]
: 100%/255 (-255 to +255)
•
F3-03 = 1 [12-bit]
: 100%/4095 (-4095 to +4095)
•
F3-03 = 2 [16-bit]
: 100%/30000 (-33000 to +33000)
8 : Multi-Function Digital Input
The DI-A3 option is also used as a multi-function digital input terminal.
When the DI-A3 option is not installed in the drive and
F3-01 = 8
, these functions are enabled:
•
H1-40 [Mbus Reg 15C0h bit0 Input Func] to H1-42 [Mbus Reg 15C0h bit2 Input Func]
•
H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]
■
F3-03: Digital Input Data Length Select
No.
(Hex.)
Name
Description
Default
(Range)
F3-03
(03B9)
Digital Input Data Length
Select
Sets the number of bits to set the frequency reference with
DI-A3
.
2
(0 - 2)
0 : 8-bit
1 : 12-bit
2 : 16-bit
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...