The drive detects
dEv
when the difference (speed deviation) between the frequency reference and the actual motor
speed exceeds the value set in
F1-10 [Speed Deviation Detection Level]
for an amount of time longer than the
time set in
F1-11 [Speed Deviation Detect DelayTime]
.
0 : Ramp to Stop
The drive ramps the motor to stop according to the deceleration time. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF.
1 : Coast to Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC will turn ON, and
MB-MC will turn OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor using the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF.
3 : Alarm Only
The keypad shows
dEv
, and the drive continues operation. Due to potential damage to motor and machinery,
refrain from using this setting except under special circumstances. The output terminal set for
Alarm [H2-01 to
H2-05 = 10]
switches ON.
■
F1-05: Encoder 1 Rotation Selection
No.
(Hex.)
Name
Description
Default
(Range)
F1-05
(0384)
Encoder 1 Rotation
Selection
Sets the output sequence for the A and B pulses from the encoder, assuming that the motor is
operating in the forward direction.
Determined by A1-02
(0, 1)
Refer to the installation manual included with the option card for more information on how to confirm and set the
encoder pulse output sequence.
0 : Pulse A leads in FWD Direction
1 : Pulse B leads in FWD Direction
■
F1-06: Encoder 1 Pulse Monitor Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F1-06
(0385)
Encoder 1 Pulse Monitor
Scaling
Sets the ratio between the pulse input and the pulse output of the encoder as a 3-digit number. The
first digit is the numerator and the second and third digits set the denominator.
001
(001 - 032, 102 - 132 (1 - 1/
32))
When the setting value is a 3-digit value (xyz), the dividing ratio is (1 + x)/yz
For example, when
F1-06 = 032
, the dividing ratio is 1/32.
Note:
When you use a single-pulse encoder, the dividing ratio for the monitor signal is 1:1
■
F1-08: Overspeed Detection Level
No.
(Hex.)
Name
Description
Default
(Range)
F1-08
(0387)
Overspeed Detection Level
Sets the detection level of
oS [Overspeed]
as a percentage when the maximum output frequency
is 100%.
115%
(0 - 120%)
When the motor speed is more than the value set in
F1-08
for longer than the time set in
F1-09 [Overspeed
Detection Delay Time]
, the drive will detect
oS
.
■
F1-09: Overspeed Detection Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
F1-09
(0388)
Overspeed Detection Delay
Time
Sets the length of time that the speed feedback must be more than the
F1-08
level to cause
oS
[Overspeed]
.
Determined by A1-02
(0.0 - 2.0 s)
When the motor speed is more than the value set in
F1-08 [Overspeed Detection Level]
for longer than the time
set in
F1-09
, the drive will detect
oS
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...