E3: V/f Pattern for Motor 2
E3 parameters [V/f Pattern for Motor 2]
set the control mode and V/f pattern used for motor 2.
Note:
V/f preset patterns equivalent to those set with
E1-03 [V/f Pattern Selection]
are not available for
E3 parameters
. Use
E3-04 [Motor 2
Maximum Output Frequency]
to
E3-10 [Motor 2 Minimum Output Voltage]
to manually set the V/f pattern.
■
Notes on Manually Setting V/f Patterns
Figure 11.48 Motor 2 V/f Pattern Diagram
•
To configure a linear V/f pattern at frequencies lower than
E3-06 [Motor 2 Base Frequency]
, set
E3-07 = E3-09
[Motor 2 Mid Point A Frequency = Motor 2 Minimum Output Frequency]
. In this application, the drive ignores
E1-08 [Mid Point A Voltage]
.
•
Set the five frequencies as specified by these rules:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 [Motor 2 Minimum Output Frequency ≤ Motor 2 Mid Point A
Frequency < Motor 2 Base Frequency ≤ Motor 2 Mid Point B Frequency ≤ Motor 2 Maximum Output
Frequency]
Incorrect settings will trigger
oPE10 [V/f Data Setting Error]
.
•
If
E3-11 = 0.0 Hz
, the drive will ignore the V/f pattern settings.
•
When you use
A1-03 [Initialize Parameters]
to initialize the drive, the drive will reset the manually set values
for
E3-04 to E3-13 [Motor 2 Base Voltage]
to default values.
■
E3-01: Motor 2 Control Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
E3-01
(0319)
Motor 2 Control Mode
Selection
Sets the control method for motor 2.
2
(0 - 3)
Note:
•
Changing the motor 2 control mode selection changes the settings value of parameters dependent on
E3-01
to the default settings.
•
Parameter
L1-01 [Motor Overload (oL1) Protection]
sets the protection operation of
oL1 [Motor Overload]
the same as Motor 1.
•
When you use parameter
A1-03 [Initialize Parameters]
to initialize the drive, this parameter is not reset.
0 : V/f Control
1 : Closed Loop V/f control
2 : Open Loop Vector control
3 : Closed Loop Vector control
■
E3-04: Motor 2 Maximum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E3-04
(031A)
Motor 2 Maximum Output
Frequency
Set the maximum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(40.0 - 590.0 Hz)
■
E3-05: Motor 2 Maximum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E3-05
(031B)
Motor 2 Maximum Output
Voltage
Sets the maximum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...