642
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
E2-02: Motor Rated Slip
No.
(Hex.)
Name
Description
Default
(Range)
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
Determined by o2-04
(0.000 - 20.000 Hz)
The setting value of
E2-02
is the slip compensation reference value. The drive sets this parameter during the
Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning). If Auto-Tuning cannot be performed,
calculate the motor rated slip using the information written on the motor nameplate and the formula below:
E2-02
= f - (n × p) / 120
•
f: Motor rated frequency (Hz)
•
n: Rated motor speed (min
-1
(r/min))
•
p: Number of motor poles
■
E2-03: Motor No-Load Current
No.
(Hex.)
Name
Description
Default
(Range)
E2-03
(0310)
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency and the no-
load voltage.
Determined by o2-04
(0 - E2-01)
Note:
The units for the default setting and setting range vary depending on the model of the drive.
•
2003 to 2033, 4002 to 4018: 0.01 A units
•
2047 to 2415, 4024 to 4605: 0.1 A units
The drive sets this parameter during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-
Tuning). The motor no-load current listed in the motor test report can also be entered to E2-03 manually. Contact
the motor manufacturer to receive a copy of the motor test report.
Note:
The default setting of the no-load current is for performance with a 4-pole motor recommended by Yaskawa.
■
E2-04: Motor Pole Count
No.
(Hex.)
Name
Description
Default
(Range)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 120)
Note:
•
When
A1-02 = 0, 1, 3 [Control Method Selection = V/f, CL-V/f, CLV]
, the maximum value is 120.
•
When
A1-02 = 2, 4 [OLV, AOLV]
, the maximum value is 48.
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
■
E2-05: Motor Line-to-Line Resistance
No.
(Hex.)
Name
Description
Default
(Range)
E2-05
(0312)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
Note:
This value is the motor line-to-line resistance. Be careful not to set this parameter with the single phase resistance.
If Auto-Tuning completes successfully, this value is automatically calculated. If Auto-Tuning cannot be executed,
obtain a test report from the motor manufacturer. Use the information found on the motor nameplate with any of
the following formulas to calculate the motor line-to-line resistance.
•
E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
•
B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
•
F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...