E1-10: Minimum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
■
E1-11: Mid Point B Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
Note:
Set this parameter to
0.0
to disable the function.
■
E1-12: Mid Point B Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-12
(030B)
Expert
Mid Point B Voltage
Sets a middle point voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
Note:
Set this parameter to
0.0
to disable the function.
■
E1-13: Base Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)
Note:
•
After Auto-Tuning, the value of
E1-13
=
E1-05 [Maximum Output Voltage]
.
•
When
E1-13 = 0.0
, use the value of
E1-05
to control the voltage.
■
E1-14: Middle Out Freq Volt Select 1
No.
(Hex.)
Name
Description
Default
(Range)
E1-14
(034C)
Middle Out Freq Volt Select
1
Sets the mid point A voltage for reverse run used when
b1-23 = 1 [Selection REV Parameters =
Enabled]
.
Determined by A1-02 and
E1-03
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E1-15: Minimum Out Freq Volt Select 1
No.
(Hex.)
Name
Description
Default
(Range)
E1-15
(034D)
Minimum Out Freq Volt
Select 1
Sets the minimum output voltage for reverse run used when
b1-23 = 1 [Selection REV
Parameters = Enabled]
.
Determined by A1-02 and
E1-03
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E1-16: Middle Out Freq Volt Select 2
No.
(Hex.)
Name
Description
Default
(Range)
E1-16
(034E)
Middle Out Freq Volt Select
2
Sets the mid point A voltage used when
H1-xx = 38 [MFDI Function Selection = Counterweight
Selection]
.
Determined by A1-02 and
E1-03
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...