2.3 Installation Orientation and Spacing
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
35
A - At least 50 mm (2 in.)
B - At least 30 mm (1.2 in.) on both sides
C - At least 2 mm (0.08 in.) between each drive
D - At least 120 mm (4.7 in.) above and below
Figure 2.3 Drive Installation Space (Side-by-Side Mounting)
Note:
•
If the dimensions of the drives differ when using a side-by-side installation, then line up the tops of all the drives. This makes it easier
to replace the cooling fan later.
•
If mounting an enclosed wall-mounted type (UL Type 1) drive using a side-by-side installation, completely remove the top protective
cover for the drive. Refer to
“
Attach the Top Protective Cover
”
to remove the top protective cover.
Figure 2.4 Enclosed Wall-Mounted Type (UL Type 1) Side-by-Side Mounting