344
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Code
Name
Causes
Possible Solutions
CP1
Comparator 1 Limit Fault
The monitor value set in
H2-20 [Comparator 1
Monitor Selection]
was within the range of
H2-21
[Comparator 1 Lower Limit]
and
H2-22
[Comparator 1 Upper Limit]
.
Examine the monitor value setting and remove the cause of the
fault.
Note:
•
This fault is detected when the terminal is assigned to
H2-01 to H2-05 = 66 [MFDO Function Select = Comparator1]
.
•
Do a Fault Reset to clear the fault.
•
Set the stopping method for this fault in
H2-33 [Comparator1 Protection Selection]
.
Code
Name
Causes
Possible Solutions
CP2
Comparator 2 Limit Fault
The monitor value set in
H2-26 [Comparator 2
Monitor Selection]
was outside the range of
H2-27
[Comparator 2 Lower Limit]
and
H2-28
[Comparator 2 Upper Limit]
.
Examine the monitor value setting and remove the cause of the
fault.
Note:
•
This fault is detected when the terminal is assigned to
H2-01 to H2-05 = 67 [MFDO Function Select = Comparator2]
.
•
Do a Fault Reset to clear the fault.
•
Set the stopping method for this fault in
H2-35 [CP2 Protection Selection]
.
Code
Name
Causes
Possible Solutions
CPF00 to
CPF03, CPF07
to CPF08,
CPF11 to
CPF14, CPF16
to CPF24, and
CPF26 to
CPF39
Control Circuit Error
A drive hardware problem occurred.
•
Re-energize the drive.
•
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact
Yaskawa or your nearest sales representative.
Note:
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for these faults.
Code
Name
Causes
Possible Solutions
CPF06
EEPROM Memory Data Error
The drive power supply was switched off while the
parameter Write command was entered from a
communications option card.
Set
A1-03 = 2220 [Initialize Parameters = 2-Wire initialization]
and initialize the drive.
An EEPROM peripheral circuit error occurred.
•
Re-energize the drive and check if the fault still remains.
•
If the fault stays, replace the control board or the drive. For
instructions on replacing the control board, contact Yaskawa or
your nearest sales representative.
Note:
•
Detected if there is an error in the data written to the EEPROM of the drive.
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for this fault.
Code
Name
Causes
Possible Solutions
CPF25
Terminal Board not Connected
The terminal board is not correctly connected to the
drive.
1. De-energize the drive.
2. Correctly connect the terminal board to the drive.
3. Re-energize the drive.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
dEv
Speed Deviation
The load is too heavy.
Decrease the load.
Acceleration and deceleration times are set too
short.
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Time]
.
The
dEv
detection level settings are incorrect.
Adjust
F1-10 [Speed Deviation Detection Level]
and
F1-11
[Speed Deviation Detect DelayTime]
.
The load is locked up.
Examine the machine.
The holding brake is stopping the motor.
Release the holding brake.
Note:
•
The drive detects this error if the difference between the detected speed and the speed reference is more than the setting of
F1-10
for longer than
F1-11
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this error, the drive will operate the motor as specified by the stopping method set in
F1-04 [Speed Deviation Detection Select]
.
Code
Name
Causes
Possible Solutions
E5
MECHATROLINK Watchdog
Timer Err
The drive detected a watchdog circuit exception
while it received data from the controller.
Examine the MECHATROLINK cable connection. If this error
occurs frequently, examine the wiring and decrease the effects of
electrical interference as specified by these manuals:
•
MECHATROLINK-II Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP011)
•
MECHATROLINK-III Installation Manual
(MECHATROLINK Members Association, publication
number MMATDEP018)
Note:
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the stop method set in
F6-25 [MECHATROLINK Watchdog Error Sel]
.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...