YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
113
Terminal Input Signal
DIP Switch Settings
Parameters
Switch
Setting
No.
Signal Level
A1
Voltage input
-
-
H3-01
0: 0 V to 10 V/100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
A2
Voltage input
S1
V
H3-09
0: 0 V to 10 V/100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
Current input
I
(Default)
2: 4 mA to 20 mA/100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/100% (input impedance: 250 Ω)
A3
Voltage input
S4
AI
(Default)
H3-05
0: 0 V to 10 V/100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
Note:
•
To set both A1 and A2 to frequency reference, set
H3-02, H3-10 = 0 [Terminal A1 Function Selection, Terminal A2 Function Selection
= Frequency Bias]
. Both analog input values will be combined to create the frequency reference.
•
To set DIP switches, use tweezers or a jig that has a tip of approximately 0.8 mm.
•
To use terminal A3 as a voltage input terminal, set DIP switch S4 to
“
AI
”
. The default setting of DIP switch S4 is
“
AI
”
.
◆
Set Multi-Function Analog Input Terminal A3 to PTC Input
Terminal A3 can be configured either as multi-function analog input, or as PTC input for motor overload
protection.
Use DIP switch S4 to select the input function.
Figure 2.121 Location of DIP Switch S4
Terminal
Settings for DIP Switches
Description
A3
AI
(Default)
Functions as multi-function analog input terminal.
Select the function with
H3-06 [Terminal A3 Function Selection]
.
Select the signal level with
H3-05 [Terminal A3 Signal Level Select]
.
•
0: 0 V to 10 V/100% (input impedance: 20 kΩ)
•
1: -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
PTC
Functions as PTC input terminal.
Set
H3-06 = E [Motor Temperature (PTC input)]
.
Set
H3-05 = 0 [0 to 10 V]
.
◆
Select Output Signals for Multi-Function Analog Output Terminals FM, AM
The signal level for the voltage output of terminals AM and FM can be set. Set using
H4-07 and H4-08
.
Terminal
Types of Output Signals
Parameters
No.
Signal Level
FM
Voltage output
H4-07
[Terminal FM Signal Level
Select]
0: 0 to 10 Vdc (default)
1: -10 to +10 Vdc
AM
Voltage output
H4-08
[Terminal AM Signal Level
Select]
0: 0 to 10 Vdc (default)
1: -10 to +10 Vdc
◆
Switch ON Termination Resistor for MEMOBUS/Modbus Communications
Set DIP switch S2 to the ON position when the drive is the last slave in a MEMOBUS/Modbus communications.
This drive is equipped with a built-in termination resistor for the RS-485 interface.
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...