5.5 Hardware configuration - I/O modules
After the hardware configuration place the System 300 modules in the plugged sequence
starting with slot 4.
For parametrization double-click during the project engineering at the slot overview on the
module you want to parameterize. In the appearing dialog window you may set the
wanted parameters. By using the SFCs 55, 56 and 57 you may alter and transfer param-
eters for wanted modules during runtime. For this you have to store the module specific
parameters in so called "record sets". More detailed information about the structure of the
record sets is to find in the according module description.
For the project engineering of more than 8 modules you may use line interface connec-
tions. For this you set in the hardware configurator the module IM 360 from the hardware
catalog to slot 3 of your 1. profile rail. Now you may extend your system with up to 3 pro-
file rails by starting each with an IM 361 from Siemens at slot 3. Considering the max.
total current with the VIPA SPEED7 CPUs up to 32 modules may be arranged in a row.
Here the installation of the line connections IM 360/361 from Siemens is not required.
5.6 Hardware configuration - Ethernet PG/OP channel
The CPU 314-6CF23 has an integrated Ethernet PG/OP channel. This channel allows
you to program and remote control your CPU. The PG/OP channel also gives you access
to the internal web page that contains information about firmware version, connected I/O
devices, current cycle times etc. With the first start-up respectively after an overall reset
the Ethernet PG/OP channel does not have any IP address. For online access to the
CPU via Ethernet PG/OP channel valid IP address parameters have to be assigned to
this by means of the Siemens SIMATIC Manager. This is called "initialization".
1.
Install your System 300S with your CPU.
2.
Wire the system by connecting cables for voltage supply and signals.
3.
Connect the Ethernet jack of the Ethernet PG/OP channel to Ethernet
4.
Switch on the power supply.
ð
After a short boot time the CP is ready for communication. He possibly has no
IP address data and requires an initialization.
Hardware configuration of
the modules
Parametrization
Bus extension with IM 360
and IM 361
Overview
Assembly and commis-
sioning
VIPA System 300S
+
Deployment CPU 314-6CF23
Hardware configuration - Ethernet PG/OP channel
HB140 | CPU | 314-6CF23 | en | 19-01