DWG. NO. 02Y00025-0409
SHEET NO. 1 OF 5
R E L .   0 3 / 2 2 / 9 6

( m - df )

For GPD 505 Adjustable

Frequency Drives

CHANGE RECORD

Integral Mounting Option

RS-232C/485 Interface Card

Model No. CM086

Before installing this option, a TECHNICALLY QUALIFIED INDIVIDUAL, who is familiar with this type of
equipment and hazards involved, should READ this ENTIRE INSTRUCTION SHEET.

DESCRIPTION

The RS-232C/485 Interface Card CM086 (Figure 1) is mounted on the Control Board of the GPD 505 to
input/output various signals from external devices by means of RS-485 serial communication.

RECEIVING

All equipment is tested against defect at the factory.  Report any damages or shortages evident when the
equipment is received to the commercial carrier who transported the equipment.

INSTALLATION AND WIRING

WARNING

Hazardous voltage can cause severe injury or death.  Lock all power sources feeding
Drive in "OFF" position.

1.    Disconnect all electrical power to Drive.

2.    Remove Drive front cover.  Check that “CHARGE” indicator lamp inside Drive is off.

3.    Verify voltage has been disconnected by using a voltmeter to check for voltage at incoming power terminals
(L1, L2, L3).

CAUTION

The option card uses CMOS IC chips.  If proper electrostatic discharge (ESD)
protective procedure is not used when handling the card, the ICs may be damaged,
resulting in erratic performance of the drive.

4.    Refer to Figure 2.  Position the option card on four mounting spacers on the Control Board of the Drive.
Gently press the card into place until its four mounting holes click into place on the the spacers.

5.    Plug the 2CN cable from the option card into connector 2CN of the Control Board.

6.    Connect the grounding lead wire from the CM086 card to the grounding terminal on the Control Board.

Содержание CM086

Страница 1: ...ND WIRING WARNING Hazardous voltage can cause severe injury or death Lock all power sources feeding Drive in OFF position 1 Disconnect all electrical power to Drive 2 Remove Drive front cover Check that CHARGE indicator lamp inside Drive is off 3 Verify voltage has been disconnected by using a voltmeter to check for voltage at incoming power terminals L1 L2 L3 CAUTION The option card uses CMOS IC ...

Страница 2: ... W M 3 1f7 7 H 7 6X 7 f hfW W H he W e L 7 L fJ H I4 0M V4 5 3 V 5 3 W2 X 3 L W eW Y N L e 5 W2 6K 1 5 f he W hf hW2 6Xg e 1 1 f7 5 I4 0Y N V40Y V4 W X N KO O 3 1 e 0Y W 6K eO2 6K 5 H f he 7 Y 5hf N g W X f 3 e f H J W X 3 K V4 I4 0M hI4 0M I4 0 7 6 2 6X I4 M h I4 0Y L f heJ Y 0Y L f 7 1 f N e f 7 J 7 M I X V 6K V L J X hO K I H 1 f he7 Y J M 1 f 5 f J e g3 5 7 YfN 1 V4 6X N 1 W MI 1 gO2 6KfO2 6K ...

Страница 3: ... hfJ J H f I4 Hf f 5 N L I4 0Y I4 0M J W 5 3 f I4 f f J J 1 L I4 0M I4 0M N 7 Y N f Lf f 1 7 7 L hf O26K hf I4 0M J 0Y J f f f 3 3 1 he W2 hf H 7 W 0M 7 f J Hf f N N heW L he J 3 W M J f f f 3 he7 Xhe 3 7 N W Y f Lf f N he3 he N W Y N f 1f f heV Yhe 3 W Y f L N f f J 5 he V Y he 3 J N W Y f 5f e J 7 V4 0Yhf N 7 W H f H Hf e 7 3 1 W 5 f L Lf e N J J J W Y f 1f e 5 7 7 J O 0Y f H f Y 3 7 M f e J Y 3...

Страница 4: ...ONTROL PCB Grounding lead wire FACTORY CONNECTION TC1 1 2 3 4 TC2 E E P S R S R S R S R RS 485 TO HOST DEVICE R11 Termination resistor S1 OFF 2CN GPD 505 CM086 OPTION CARD I M SHIELD CONTROL PCB TC1 1 2 3 4 TC2 E E P S R S R R11 Termination resistor S1 ON SEE STEP 8 OF INSTALLATION PROCEDURETODETERMINE PROPER SETTING OF SWITCH S1 E E Figure 3 CM086 Interconnection Diagram ...

Страница 5: ...TE Parameter Selection Initialization parameter n001 needs to be set to 3 in order to view and change these parameters See section 5 16 in the GPD 505 technical manual for a further explanation of serial communications 11 Place this instruction sheet with your drive technical manual THIS COMPLETES INSTALLATION OF THIS OPTION n103 Modbus Time 0 Time out detection is 1 0 or 1 1 Out Detection disable...

Отзывы: