12.11 o: Keypad-Related Settings
744
YASKAWA
SIEPC71061753A GA500 Technical Manual
1 : Reset
Resets the values of
U4-02
,
U4-24
, and
U4-25
. After the reset, the drive automatically resets
o4-13
to
0
.
■
o4-22: Time Format
No.
(Hex.)
Name
Description
Default
(Range)
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD keypad.
0
(0 - 2)
Sets the display of the time shown in the upper-left of the LCD keypad screen.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
■
o4-23: Date Format
No.
(Hex.)
Name
Description
Default
(Range)
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when using an LCD keypad.
0
(0 - 2)
Sets the date format that the drive uses for the fault history and other records.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
■
o4-24: bAT Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-24
(310F)
RUN
bAT Detection Selection
Sets the operation when the drive detects
bAT [Keypad Battery Low Voltage]
and
TiM [Keypad
Time Not Set]
. This parameter is only available when you use an LCD keypad.
0
(0 - 2)
0 : Disable
The drive will not detect
bAT
or
TiM
.
1 : Enable (Alarm Detected)
The keypad shows
bAT
or
TiM
and the drive continues operation. The output terminal set to
Alarm [H2-01 to H2-
03 = 10]
activates.
2 : Enable (Fault Detected)
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = E]
activates.
◆
o5: Log Function
The data log function saves drive status information as a CSV file in the micro SD memory card in the keypad.
Monitors Ux-xx
are the source of data log information. You can record a maximum of 10 monitors.
Change the LCD keypad screen from the main menu to the Diagnostic Tools screen and select the data log
function. Set the number of the monitor to record and the sampling time, then start to record the data log.
Table 12.74 Setting Parameters for Data Log Items
No.
Name
Default
Data Log Monitors
o5-03
Log Monitor Data 1
101
U1-01 [Frequency Reference]
o5-04
Log Monitor Data 2
102
U1-02 [Output Frequency]
o5-05
Log Monitor Data 3
103
U1-03 [Output Current]
o5-06
Log Monitor Data 4
107
U1-07 [DC Bus Voltage]
o5-07
Log Monitor Data 5
108
U1-08 [Output Power]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...