12.11 o: Keypad-Related Settings
736
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
o1-51: Trend Plot Time Scale Setting
No.
(Hex.)
Name
Description
Default
(Range)
o1-51
(11CB)
RUN
Trend Plot Time Scale
Setting
Sets the time scale (horizontal axis) to display the trend plot. When you change this setting, the
drive automatically adjusts the data sampling time. This parameter is only available when using
an LCD keypad.
300 s
(1 - 3600 s)
■
o1-55: Analog Gauge Area Selection
No.
(Hex.)
Name
Description
Default
(Range)
o1-55
(11EE)
RUN
Analog Gauge Area
Selection
Sets the range used to display the monitor set in
o1-24 [Custom Monitor 1]
as an analog gauge.
This parameter is only available when using an LCD keypad.
1
(0, 1)
0 : +/- Area ( - o1-56 ~ o1-56 )
1 : + Area ( 0 ~ o1-56 )
■
o1-56: Analog Gauge Area Setting
No.
(Hex.)
Name
Description
Default
(Range)
o1-56
(11EF)
RUN
Analog Gauge Area Setting
Sets the value used to display the monitor set in
o1-24 [Custom Monitor 1]
as an analog meter.
This parameter is only available when using an LCD keypad.
100.0%
(0.0 - 100.0%)
■
o1-58: Motor Power Unit Selection
No.
(Hex.)
Name
Description
Default
(Range)
o1-58
(3125)
Motor Power Unit Selection
Sets the setting unit for parameters that set the motor rated power.
0
(0, 1)
The drive shows these parameter values in the set units:
•
E2-11 [Motor Rated Power]
•
E4-11 [Motor 2 Rated Power]
•
E5-02 [PM Motor Rated Power]
•
E9-07 [Motor Rated Power]
•
T1-02 [Motor Rated Power]
•
T2-04 [PM Motor Rated Power]
•
T4-08 [Motor Rated Capacity]
0 : kW
Shows the motor output in kW units.
1 : HP
Shows the motor output in HP units.
◆
o2: Keypad Operation
■
o2-01: LO/RE Key Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
o2-01
(0505)
LO/RE Key Function
Selection
Sets the function that lets you use
to switch between LOCAL and REMOTE Modes.
1
(0, 1)
0 : Disabled
You cannot use
to switch between LOCAL and REMOTE Modes.
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...