724
YASKAWA
SIEPC71061753A GA500 Technical Manual
•
If the motor does not run smoothly, gradually increase the setting from 0.
•
If the motor stalls during run at constant speed, gradually increase the setting from 0.
•
If there is vibration or hunting, decrease the setting.
Note:
•
If the value is set too low, the drive will detect
STPo [Motor Step-Out Detected]
.
•
If you use one motor or more than motor at low inertia and the value is too high, there can be vibration in the motor.
0 : Below 1:10
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is less than 1:10
•
There are large current ripples
1 : Between 1:10 and 1:30
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is approximately 1:10 to 1:30
•
Parameter
n8-55 = 0
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
2 : Between 1:30 and 1:50
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is approximately 1:30 to 1:50
•
Parameter
n8-55 = 1
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
3 : Beyond 1:50
Adjust in the following situations.
•
The ratio between the motor inertia and machine inertia is more than 1:50
•
Parameter
n8-55 = 2
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
■
n8-57: HFI Overlap Selection
No.
(Hex.)
Name
Description
Default
(Range)
n8-57
(0574)
HFI Overlap Selection
Sets the function that detects motor speed with high frequency injection.
0
(0, 1)
Note:
•
When you set
n8-57 = 1
, doHigh Frequency Injection Auto-Tuning.
•
When there is high frequency injection, the motor will make an excitation sound.
•
When you use Zero Speed Control, set
E1-09 [Minimum Output Frequency] = 0.0
.
0 : Disabled
Use this setting with SPM motors. The speed control range is approximately 1:20.
When
n8-57 = 0
, you cannot set
E1-09 [Minimum Output Frequency]
≤ 1/20 of the value of
E1-06 [Base
Frequency]
.
1 : Enabled
The speed control range changes to 1:100 to give sufficient speed detection at low speeds.
Note:
It is not available with an SPM motor.
■
n8-62: Output Voltage Limit Level
No.
(Hex.)
Name
Description
Default
(Range)
n8-62
(057D)
Expert
Output Voltage Limit Level
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not necessary
to change this parameter.
200 V Class: 200.0 V, 400
V: 400.0 V
(200 V Class: 0.0 to 230.0
V, 400 V Class: 0.0 to 460.0
V)
Set this parameter lower than the input power supply voltage.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...