12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
655
■
H5-03: Communication Parity Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-03
(0427)
Communication Parity
Selection
Sets the communications parity used for MEMOBUS/Modbus communications.
0
(0 - 2)
Note:
Restart the drive after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
■
H5-04: Communication Error Stop Method
No.
(Hex.)
Name
Description
Default
(Range)
H5-04
(0428)
Communication Error Stop
Method
Sets the motor Stopping Method when the drive detects
CE [MEMOBUS/Modbus Communication
Err]
issues.
3
(0 - 3)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 =
E]
activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. The output terminal set for
Fault
[H2-01 to H2-03 = E]
activates.
3 : Alarm Only
The keypad shows
CE
and the drive continues operation. The output terminal set for
Alarm [H2-01 to H2-03 =
10]
activates.
■
H5-05: Comm Fault Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-05
(0429)
Comm Fault Detection
Selection
Sets the function that detects
CE [Modbus Communication Error]
issues during MEMOBUS/
Modbus communications.
1
(0, 1)
If the drive does not receive data from the master during the time set in
H5-09 [CE Detection Time]
, it will detect
a
CE
error.
0 : Disabled
Does not detect
CE
. The drive continues operation.
1 : Enabled
Detects
CE
. If the drive detects
CE
, it will operate as specified by the setting of
H5-04 [Communication Error
Stop Method]
.
■
H5-06: Drive Transmit Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
H5-06
(042A)
Drive Transmit Wait Time
Sets the time to wait to send a response message after the drive receives a command message
from the master.
5 ms
(0 - 65 ms)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...