SIEPC71061753A GA500 Technical Manual
531
■
C4-04: Torque Compensation @ REV Start
No.
(Hex.)
Name
Description
Default
(Range)
C4-04
(0218)
Torque Compensation @
REV Start
Sets the amount of torque reference for reverse start as a percentage of the motor rated torque.
0.0%
(-200.0 - 0.0%)
The drive uses the time constant set in
C4-05 [Torque Compensation Time]
to do the torque compensation
function.
This is available only when you start the motor with the reverse Run command.
■
C4-05: Torque Compensation Time
No.
(Hex.)
Name
Description
Default
(Range)
C4-05
(0219)
Torque Compensation Time
Sets the starting torque constant to use with
C4-03 and C4-04 [Torque Compensation @ FWD/
REV Start]
.
10 ms
(0 - 200 ms)
■
C4-06: Motor 2 Torque Comp Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
C4-06
(021A)
Motor 2 Torque Comp
Delay Time
Sets the value if
ov [Overvoltage]
occurs with sudden changes in the load, at the end of
acceleration, or at the start of deceleration.
150 ms
(0 - 10000 ms)
Sets the time constant used during Speed Search or during regenerative operation when
ov
occurs.
Adjust this parameter in the following circumstances.
•
Gradually reduce the setting in 10 ms increments and check the performance to improve motor torque speed
response when
ov
occurs.
Note:
•
Ensure that
C4-06 ≥ C4-02 [Torque Compensation Delay Time]
.
•
Increase the setting value of
n2-03 [Automatic Freq Regulator Time 2]
proportional to
C4-06
.
■
C4-07: Motor 2 Torque Compensation Gain
No.
(Hex.)
Name
Description
Default
(Range)
C4-07
(0341)
RUN
Motor 2 Torque
Compensation Gain
Sets the gain for motor 2 torque compensation function when using the Motor Switch function.
1.00
(0.00 - 2.50)
In V/f Control, adjust the value in 0.05-unit increments for these conditions:
•
When torque is not sufficient during low-speed operation of 10 Hz or less, increase the setting value
•
When there is vibration in the motor or when the motor hunts when operating the drive with a light load,
decrease the setting value
•
When you use a long motor cable, increase the setting value.
Note:
•
Adjust
C4-07
to make sure that the output current is not more than the drive rated current during low-speed operation.
•
When
A1-02 = 2 [Control Method Selection = OLV]
, usually it is not necessary to change the setting. Torque accuracy will decrease.
■
C4-23: Current Control Gain
No.
(Hex.)
Name
Description
Default
(Range)
C4-23
(1583)
RUN
Expert
Current Control Gain
Current control gain. Usually it is not necessary to change this parameter.
1.00
(0.50 - 2.50)
◆
C5: Auto Speed Regulator (ASR)
The ASR adjusts the torque reference to decrease the difference between frequency reference and motor speed.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...