324
YASKAWA
SIEPC71061753A GA500 Technical Manual
Table 10.16 AOLV/PM Carrier Frequency and Rated Current Derating (Three-Phase 400 V)
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
4001
1.2
1.2
1.1
0.9
0.7
0.5
1.2
1.2
1.1
0.9
0.7
0.5
4002
1.8
1.8
1.7
1.4
1.1
0.8
2.1
2.0
1.7
1.4
1.1
0.8
4004
3.4
3.4
3.2
2.6
2.0
1.5
4.1
3.8
3.2
2.6
2.0
1.5
4005
4.8
4.8
4.5
3.7
2.9
2.1
5.4
5.3
4.5
3.7
2.9
2.1
4007
5.5
5.5
5.2
4.2
3.3
2.4
7.1
6.2
5.2
4.3
3.3
2.4
4009
7.3
7.3
6.9
5.6
4.4
3.1
8.9
8.1
6.9
5.6
4.4
3.1
4012
9.2
9.2
8.7
7.1
5.5
3.9
11.9
10.3
8.7
7.1
5.5
3.9
4018
14.8
14.8
14.0
11.4
8.9
6.3
17.8
16.4
15.2
11.4
8.8
6.3
4023
18.0
18.0
17.0
13.9
10.8
7.7
23.4
20.3
17.1
14.0
10.8
7.7
4031
24.0
24.0
22.6
18.5
14.4
10.3
31.0
26.9
22.7
18.6
14.4
10.3
4038
31.0
31.0
29.2
23.9
18.6
13.3
38.0
34.5
29.2
23.9
18.6
13.3
4044
39.0
39.0
36.8
30.1
23.4
16.7
44.0
43.5
36.8
30.1
23.4
16.7
4060
45.0
45.0
42.4
34.7
27.0
19.3
60.0
51.8
43.5
35.3
27.0
18.8
◆
Derating Depending on Ambient Temperature
When you install drives in a place where ambient temperatures are higher than the rated conditions or install
drives side-by-side in the enclosure panel, set
L8-12 [Ambient Temperature Setting]
and
L8-35 [Installation
Method Selection]
. Derate the output current as specified in
No.
(Hex.)
Name
Description
Default
(Range)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(-10 °C - +60 °C)
No.
(Hex.)
Name
Description
Default
(Range)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
0
(0 - 3)
0 : IP20/UL Open Type
Use this setting to install IP20/UL Open Type drives.
Make sure that there is 30 mm (1.18 in) minimum of space between drives or between the drive and side of the
enclosure panel.
1 : Side-by-Side Mounting
Use this setting to install more than one drive side-by-side.
2 : IP20/UL Type 1/IP55
Use this setting to install IP20/UL Type 1 drives or IP55 drives.
3 : External Heatsink
Use this setting when the heatsink (cooling fin) is outside the control panel.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...