7.10 Troubleshooting Without Fault Display
YASKAWA
SIEPC71061753A GA500 Technical Manual
281
Causes
Possible Solutions
An incorrect password was entered in
A1-04 [Password]
.
•
Enter the correct password to
A1-04
again.
•
If you forgot the password, set the password again with
A1-04
and
A1-05 [Password Setting]
.
Note:
If the password is set, it will not be possible to change these parameters until the password
matches:
•
A1-01 [Access Level Selection]
•
A1-02 [Control Method Selection]
•
A1-03 [Initialize Parameters]
•
A1-06 [Application Preset]
•
A1-07 [DriveWorksEZ Function Selection]
•
A2-01 to A2-32 [User Parameter 1 to User Parameter 32]
The drive detected
Uv [Undervoltage]
.
•
View
U1-07 [DC Bus Voltage]
to see the power supply voltage.
•
Examine the main circuit wiring.
◆
The Motor Does Not Rotate After Entering Run Command
Causes
Possible Solutions
The drive is not in Drive Mode.
1.
Make sure that the READY LED on the keypad is on.
2.
If the READY LED is off, push and hold the ESC Key to go back to the frequency reference
screen (the initial screen).
The drive stopped and you pushed
to transfer the Run command
source to the keypad.
Do one of these two:
•
Push
.
•
Re-energize the drive.
Note:
Set
o2-01 = 0 [LO/RE Key Function Selection = Disabled]
to prevent changing the Run
command source with
.
Auto-Tuning completed.
Push and hold the ESC Key to go back to the frequency reference screen (the initial screen).
Note:
When Auto-Tuning completes, the drive changes to Programming Mode. The drive will not
accept a Run command unless the drive is in Drive Mode.
The drive received a Fast Stop command.
Turn off the fast stop input signal.
The settings for the source that supplies the Run command are incorrect.
Set
b1-02 [Run Command Selection 1]
correctly.
The frequency reference source is set incorrectly.
Set
b1-01 [Frequency Reference Selection 1]
correctly.
There is defective wiring in the control circuit terminals.
•
Correctly wire the drive control circuit terminals.
•
View
U1-10 [Input Terminal Status]
for input terminal status.
The settings for voltage input and current input of the master frequency
reference are incorrect.
Examine these analog input terminal signal level settings:
•
Terminal A1:
H3-01 [Terminal A1 Signal Level Select]
•
Terminal A2: DIP switch S1 and
H3-09 [Terminal A2 Signal Level Select]
The selection for the sinking/sourcing mode and the internal/external power
supply is incorrect.
•
For sinking mode, close the circuit between terminals SC-SP with a wire jumper.
•
For sourcing mode, close the circuit between terminals SC-SN with a wire jumper.
•
For external power supply, remove the wire jumper.
The frequency reference is too low.
•
View
U1-01 [Freq Reference]
.
•
Increase the frequency reference to a value higher than
E1-09 [Minimum Output Frequency]
.
The MFAI setting is incorrect.
•
Make sure that the functions set to the MFAI are correct. The frequency reference is 0 when
H3-02, H3-10 = 1 [MFAI Function Select = Frequency Gain]
and voltage (current) is not
input.
•
Use
U1-13, U1-14 [Terminal A1, A2 Input Voltage]
to make sure that the analog input values
set to terminals A1 and A2 are applicable.
You pushed
.
Turn the Run command OFF then ON from an external input.
Note:
When you push
during operation, the drive will ramp to stop. Set
o2-02 = 0 [STOP
Key Function Selection = Disabled]
to disable the
function.
The 2-wire sequence and 3-wire sequence are set incorrectly.
•
Set one of the parameters
H1-03 to H1-07 [Terminals S3 to S7 Function Select]
to
0 [3-Wire
Sequence]
to enable the 3-wire sequence.
•
If a 2-wire sequence is necessary, make sure that
H1-03 to H1-07 ≠ 0
.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...