![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 271](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765271.webp)
YASKAWA
SIEPC71061753A GA500 Technical Manual
271
Code
Name
Causes
Possible Solutions
oPE08
Parameter Selection Error
A function was set that is not compatible with the
control method selected in
A1-02 [Control Method
Selection]
.
1.
Push ENTER Key to show
U1-18 [oPE Fault Parameter]
,
and find parameters that are not in the applicable setting
range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
When
A1-02 = 2 [OLV]
, you used these parameter
settings:
•
n2-02 > n2-03 [Automatic Freq Regulator Time
1 > Automatic Freq Regulator Time 2]
•
C4-02 > C4-06 [Torque Compensation Delay
Time > Motor 2 Torque Comp Delay Time]
•
Set
n2-02 < n2-03
.
•
Set
C4-02 < C4-06
.
When
A1-02 = 0 [V/f]
, you used these parameter
settings:
•
H6-01 = 3 [Terminal RP Pulse Train Function =
Speed Feedback (V/F Control)]
•
H1-xx = 16 [MFDI Function Select = Motor 2
Selection]
Correct the parameter settings.
Note:
You cannot use Speed Feedback (V/F Control) with the Motor
Switch function.
When
A1-02 = 5 [OLV/PM]
, you set
E5-02 to E5-
07 [PM Motor Parameters] = 0
.
•
Set
E5-01 [PM Motor Code Selection]
correctly as specified
by the motor.
•
For specialized motors, refer to the motor test report and set
E5-xx
correctly.
When
A1-02 = 5, 6 [OLV/PM, AOLV/PM]
, you
used these parameter settings:
•
E5-09 = 0.0 [PM Back-EMF Vpeak (mV/(rad/s))
= 0.0 mV/(rad/s)]
•
E5-24 = 0.0 [PM Back-EMF L-L Vrms (mV/rpm)
= 0.0 mV/min
-1
]
Set
E5-09
or
E5-24
to the correct value.
When
A1-02 = 5, 6
, you set
E5-09 ≠ 0
and
E5-24 ≠
0
.
Set
E5-09 = 0
or
E5-24 = 0
.
When
A1-02 = 6
, you set these parameters:
•
n8-57 = 0 [HFI Overlap Selection = Disabled]
•
You set
E1-09 [Minimum Output Frequency]
<
the 5% value of
E1-06
.
Correct the parameter settings.
When
A1-02 = 6
, you set these parameters:
•
n8-35 = 0 [Initial Pole Detection Method =
Pull-in]
•
n8-57 = 1 [Enabled]
Correct the parameter settings.
When
A1-02 = 8 [EZOLV]
, you used these
parameter settings:
•
E9-01 = 1, 2 [Motor Type Selection =
Permanent Magnet (PM), Synchronous
Reluctance (SynRM)]
•
b3-24 = 2 [Speed Search Method Selection =
Current Detection 2]
When
E9-01 = 1 or 2
,
set b3-24 = 1 [Speed Estimation]
.
Code
Name
Causes
Possible Solutions
oPE09
PID Control Selection Fault
These parameters are set at the same time:
•
b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠
0.0 Hz]
•
b1-03 = 2, 3 [Stopping Method Selection = DC
Injection Braking to Stop, Coast to Stop with
Timer]
•
Set
b5-15 ≠ 0.0
.
•
Set
b1-03 = 0, 1 [Ramp to Stop, Coast to Stop]
.
These parameters are set at the same time:
•
b5-01 = 1, 2 [Enabled (Standard), Enabled (D =
Feedforward)]
•
d2-02 ≠ 0.0 [Frequency Reference Lower Limit
≠ 0.0%]
Correct the parameter settings.
These parameters are set at the same time:
•
b5-01 = 1, 2 [Enabled (Standard), Enabled (D =
Feedforward)]
•
b5-11 = 1 [PID Output Reverse Selection =
Negative Output Accepted]
Correct the parameter settings.
These parameters are set at the same time:
•
b5-01 = 3, 4 [Trim (Fref+PID Out, D = Fdbk),
Trim (Fref+PID Out, D = FeedFwd)]
•
d2-02 ≠ 0.0
has been set.
Correct the parameter settings.
Note:
The drive detects this error if the PID control function selection is incorrect.
(When
b5-01 = 1 to 4 [PID Mode Setting = PID Control Enabled]
)
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...