![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 252](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765252.webp)
252
YASKAWA
SIEPC71061753A GA500 Technical Manual
Code
Name
Causes
Possible Solutions
oFA10, oFA11
Option Card Error Occurred at
Option Port (CN5)
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA12 to
oFA17
Option Card Connection Error
(CN5)
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA30 to
oFA43
Communication Option Card
Connection Error (CN5)
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oH
Heatsink Overheat
The ambient temperature is high and the heatsink
temperature of the drive is more than the value set
in
L8-02 [Overheat Alarm Level]
.
•
Measure the ambient temperature.
•
Increase the airflow in the control panel.
•
Install a cooling device (cooling fan or air conditioner) to
lower the ambient temperature.
•
Remove objects near the drive that are producing too much
heat.
The load is too heavy.
•
Measure the output current.
•
Decrease the load.
•
Decrease the value set in
C6-02 [Carrier Frequency
Selection]
.
The internal cooling fan of the drive stopped.
1.
Use the procedures in this manual to replace the cooling fan.
2.
Set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
.
Note:
•
The drive detects this fault if the heatsink temperature of the drive is more than the value set in
L8-02
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in
L8-03 [Overheat Pre-Alarm Selection]
.
Code
Name
Causes
Possible Solutions
oH1
Heatsink Overheat
The ambient temperature is high and the heatsink
temperature of the drive is more than the
oH1
detection level.
•
Measure the ambient temperature.
•
Increase the airflow in the control panel.
•
Install a cooling device (cooling fan or air conditioner) to
lower the ambient temperature.
•
Remove objects near the drive that are producing too much
heat.
The load is too heavy.
•
Measure the output current.
•
Decrease the load.
•
Decrease the value set in
C6-02 [Carrier Frequency
Selection]
.
Note:
•
The drive detects this fault if the heatsink temperature of the drive is more than the
oH1
detection level.
o2-04 [Drive Model (KVA) Selection]
determines the
oH1
detection
level.
•
Do a Fault Reset to clear the fault.
•
L5-08 [Fault Reset Enable Select Grp2]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
oH3
Motor Overheat (PTC Input)
The thermistor wiring that detects motor
temperature is defective.
Correct wiring errors.
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...