![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 248](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765248.webp)
248
YASKAWA
SIEPC71061753A GA500 Technical Manual
Code
Name
Causes
Possible Solutions
EF3
External Fault (Terminal S3)
MFDI terminal S3 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal S3.
External Fault [H1-03 = 20 to 2B]
is set to MFDI
terminal S3, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF4
External Fault (Terminal S4)
MFDI terminal S4 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal S4.
External Fault [H1-04 = 20 to 2B]
is set to MFDI
terminal S4, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF5
External Fault (Terminal S5)
MFDI terminal S5 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal S5.
External Fault [H1-05 = 20 to 2B]
is set to MFDI
terminal S5, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF6
External Fault (Terminal S6)
MFDI terminal S6 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal S6.
External Fault [H1-06 = 20 to 2B]
is set to MFDI
terminal S6, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF7
External Fault (Terminal S7)
MFDI terminal S7 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal S7.
External Fault [H1-07 = 20 to 2B]
is set to MFDI
terminal S7, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
Err
EEPROM Write Error
There was a problem with the EEPROM hardware.
•
Re-energize the drive.
•
If the fault stays, replace the control board or the drive.
Contact Yaskawa or your nearest sales representative to
replace the board.
Electrical interference corrupted the data while it
was writing to the EEPROM of the drive.
•
Push ENTER Key.
•
Set the parameters again.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
FbH
Excessive PID Feedback
The
FbH
detection level is set incorrectly.
Adjust
b5-36 [PID High Feedback Detection Lvl]
and
b5-37 [PID
High Feedback Detection Time]
.
There is a problem with the PID feedback wiring.
Correct errors with the PID control wiring.
The feedback sensor is not operating correctly.
Examine the sensors on the control device side.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...