Three-Phase 200 V Class
Table 5.16 Factory-Recommended Branch Circuit Protection: Three-Phase 200 V Class
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, CC, and T Fuse
Rated Current
A
Model
Input Rated Current
A
2001
0.18 (1/6)
0.1 (1/6)
3
FWH-25A14F
25
2002
0.37 (1/4)
0.25 (1/4)
6
FWH-25A14F
25
2004
0.75 (3/4)
0.55 (1/2)
6
FWH-25A14F
25
2006
1.1 (1.5)
0.75 (1)
10
FWH-25A14F
25
2010
2.2 (3)
1.5 (2)
20
FWH-70B
70
2012
3.0 (4)
2.2 (3)
25
FWH-70B
70
2021
5.5 (5)
4.0 (5)
40
FWH-90B
90
2030
7.5 (10)
5.5 (7.5)
-
FWH-100B
100
2042
11 (15)
7.5 (10)
-
FWH-150B
150
2056
15 (20)
11 (15)
-
FWH-200B
200
2070
18.5 (25)
15 (20)
-
FWH-200B
200
2082
22 (30)
18.5 (25)
-
FWH-225A
225
Single-Phase 200 V Class
Table 5.17 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, T, and CC Fuse
Rated Current
A
Model
Input Rated Current
A
B001
0.18 (1/6)
0.1 (1/6)
3
FWH-25A14F
25
B002
0.37 (1/4)
0.25 (1/4)
6
FWH-25A14F
25
B004
0.75 (3/4)
0.55 (1/2)
10
FWH-60B
60
B006
1.1 (1.5)
1.1 (1)
15
FWH-80B
80
B010
2.2 (3)
1.5 (2)
25
FWH-100B
100
B012
3.0 (3)
2.2 (3)
30
FWH-125B
125
B018
-
4.0 (5)
-
FWH-150B
150
Three-Phase 400 V Class
Table 5.18 Factory-Recommended Branch Circuit Protection: Three-Phase 400 V Class
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, CC, and T Fuse
Rated Current
A
Model
Input Rated Current
A
4001
0.37 (1/2)
0.37 (1/2)
3
FWH-40B
40
4002
0.75 (1)
0.55 (3/4)
6
FWH-40B
40
4004
1.5 (2)
1.1 (2)
10
FWH-50B
50
4005
2.2 (3)
1.5 (3)
10
FWH-70B
70
4007
3.0 (4)
2.2 (3)
15
FWH-70B
70
4009
4.0 (5)
3.0 (4)
20
FWH-90B
90
4012
5.5 (7.5)
4.0 (5)
25
FWH-90B
90
4018
7.5 (10)
5.5 (10)
-
FWH-80B
80
4023
11.0 (15)
7.5 (10)
-
FWH-100B
100
4031
15.0 (20)
11.0 (15)
-
FWH-125B
125
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...