3.4 Wiring Main Circuit Terminals
YASKAWA ELECTRIC
TOEP C710656 01C YASKAWA - RC5 Instruction Manual
31
◆
Closed-Loop Connectors Size
Yaskawa recommends using closed-loop crimp terminals.
UL/cUL approval requires the use of closed-loop crimp terminals when wiring the main circuit terminals.
Use only the tools recommended by the terminal manufacturer for crimping.
Table 3.6 Closed Loop Connectors Sizes (JIS C 2805) (For 200 V/400 V classes)
Note:
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line voltage drop is calculated as follows:
(If there is a possibility of excessive voltage drop, use a larger wire suitable to the required length.)
Line voltage drop (V) = 3 x wire resistance (
Ω
/km) x wire length (m) x current (A) x 10
-3
Wire Size
Terminal Screw
Tightening Torque (N•m)
Closed Loop Connectors
mm
2
AWG
0.5
20
M3.5
M4
0.8 to 1.0
1.2 to 1.4
R1.25-3.5
R1.25-4
0.75
18
1.25
16
2
14
M4
1.2 to 1.4
R2-4
M5
2.1 to 2.5
R2-5
3.5
12
M4
1.2 to 1.4
3.5-4
M5
2.1 to 2.5
3.5-R5
5.5
10
M4
1.2 to 1.4
R5.5-4
M5
2.1 to 2.5
R5.5-5
8
8
M5
2.1 to 2.5
R8-5
M6
3.6 to 5.1
R8-6
14
6
M6
3.6 to 5.1
R14-6
22
4
M8
8.2 to 10.2
R22-8
30/38
3/2
M8
8.2 to 10.2
R38-8
30/38
3/2
M10
18 to 23
R38-10
50/60
1/1/0
R60-10
80
3/0
R80-10
100
4/0
R100-10
100
4/0
M12
31.5 to 39.5
R100-12
150
300
R150-12
200
400
R200-13