u
d: References
Reference parameters are used to set the various frequency reference values during operation.
No.
Name
Description
Range Def. Mode Addr.
Hex
Pg.
d1: Frequency Reference
Use d1 parameters to configure the drive frequency reference.
d1-01
Frequency
Reference 1
Frequency reference.
d1-01 as the main frequency reference.
0.00 to
400.00
Hz
0.00
Hz
S
280
d1-02
Frequency
Reference 2
Frequency reference when digital input "Multi-Step
Speed Reference 1" (H1-
oo
= 3) is on.
0.00
Hz
S
281
d1-03
Frequency
Reference 3
Frequency reference when digital input "Multi-Step
Speed Reference 2” (H1-
oo
= 4) is on.
0.00
Hz
S
282
d1-04
Frequency
Reference 4
Frequency reference when digital inputs "Multi-Step
Speed Reference 1, 2" (H1-
oo
= 3 and 4) are on.
0.00
Hz
S
283
d1-05
Frequency
Reference 5
Frequency reference when digital input "Multi-Step
Speed Reference 3" (H1-
oo
= 5) is on.
0.00
Hz
O
284
–
d1-06
Frequency
Reference 6
Frequency reference when digital inputs "Multi-Step
Speed Reference 1, 3 " (H1-
oo
= 3 and 5) are on.
0.00
Hz
O
285
–
d1-07
Frequency
Reference 7
Frequency reference when digital inputs "Multi-Step
Speed Reference 2, 3" (H1-
oo
= 4 and 5) are on.
0.00
Hz
O
286
–
d1-08
Frequency
Reference 8
Frequency reference when multi-function input
"Multi-Step speed reference 1, 2, 3" (H1-
oo
= 3, 4,
5) are on.
0.00
Hz
O
287
–
d1-17
Jog Frequency
Reference
Frequency reference when digital inputs "Jog
Frequency Reference", "Forward Jog" or "Reverse
Jog." are on.
6.00
Hz
S
292
–
d2: Frequency Upper and Lower Limits
Use d2 parameters to configure the frequency reference limits.
d2-01
Frequency
Reference
Upper Limit
Sets the frequency reference upper limit as a
percentage of maximum output frequency (E1-04).
Output speed is limited to this value even if the
frequency reference is higher. This limit applies to all
frequency reference sources.
0.0 to
110.0
100.
0%
O
289
–
d2-02
Frequency
Reference
Lower Limit
Sets the frequency reference lower limit as a
percentage of maximum output frequency (E1-04).
Output speed is limited to this value even if the
frequency reference is lower. This limit applies to all
frequency reference sources.
0.0 to
110.0
0.0%
O
28A
–
d3: Jump Frequency
Use d3 parameters to configure the drive Jump Frequency settings.
B.2 Parameter Table
228
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual