u
b: Application
Application parameters configure the Run Command Source, DC Injection Braking, and other
application-related settings.
No.
Name
Description
Range Def. Mode Addr.
Hex
Pg.
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01
Frequency
Reference
Selection
Selects the frequency reference input source.
0: Digital Operator - Digital preset speed d1-01 to
d1-08
1: Terminals - Analog input terminal A1
2: MEMOBUS/Modbus communications (option)
3: Potentiometer (option)
0 to 3
1
S
180
b1-02
Run
Command
Selection
Selects the run command input source.
0: Digital Operator - RUN and STOP keys on the
digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications (option)
0 to 2
1
S
181
b1-03
Stopping
Method
Selection
Selects the stopping method when the run command
is removed.
0: Ramp to Stop
1: Coast to Stop
0, 1
0
S
182
b1-04
Reverse
Operation
Selection
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
0, 1
0
O
183
–
b1-07
LOCAL/
REMOTE Run
Selection
Determines the operation when the Run command
source is switched from LOCAL to REMOTE or
between REMOTE and MEMOBUS/Modbus
communication.
0: External Run command has to be cycled at the new
source to be activated.
1: External Run command at new source is accepted
immediately.
0, 1
0
O
186
–
b1-08
Run
Command
Selection
while in
Programming
Mode
0: Run command accepted only in the operation
menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during Run
0 to 2
0
O
187
–
b1-14 Phase Order
Selection
Sets the phase order for drive output terminals U/T1,
V/T2 and W/T3.
0 : Standard
1 : Switch phase order
0, 1
0
O
1C3
–
b1-17
Run
Command at
Power Up
Determines the operation when a Run command is
active at power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
0, 1
0
O
1C6
–
B.2 Parameter Table
224