At least two analog input terminals are set to the same function (i.e., at least
two of these parameters have the same setting: H3-02, H3-06, or H3-10).
Change the settings to H3-02, H3-06, and H3-10 so that functions no longer
conflict.
Note:
Both 0 (Frequency Reference Bias) and F (Not Used) can be
set to H3-02, H3-06, and H3-10 simultaneously.
The following simultaneous contradictory settings:
• H3-02, H3-06, or H3-10 = B (PID Feedback) while H6-01
(Pulse Train Input) = 1 (PID Feedback)
• H3-02, H3-06, or H3-10 = C (PID Target Value) while H6-01 = 2
(pulse train input sets the PID target value)
• H3-02, H3-06, or H3-10 = C (PID Target Value) while b5-18 = 1
(enables b5-19 as the target PID value)
• H6-01 = 2 (PID target) while b5-18 = 1
(enables b5-19 as the target PID value)
Disable one of the PID selections.
Digital Operator Display
Error Name
oPE08
Parameter Selection Error
A function has been set that cannot be used in the motor control method
selected.
Cause
Possible Solutions
Attempted to use a function that is not valid for the selected control mode. Check the motor control method and the functions available.
In OLV, n2-02 is longer than n2-03
Adjust parameter values so n2-02 is shorter than n2-03.
In OLV, C4-02 is longer than C4-06
Adjust parameter values so C4-02 is shorter than C4-06.
The following settings have occurred in OLV/PM:
• E5-03 does not equal 0
• E5-09 and E5-24 are both equal to 0, or neither equals 0
• Set E5-09 or E5-24 to the correct value, and set the other to 0.
• Set the motor rated current for PM to 0 (E5-03).
b1-14 (Phase Order Selection) is set to 1 (Switch phase order) when using a
PG option card.
Correct the parameter settings.
Note:
Use U1-18 to find parameters that are set outside the specified setting range. When multiple errors occur simultaneously, other errors are
given precedence over oPE08.
Digital Operator Display
Error Name
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is
enabled (b5-01 = 1 to 4).
Cause
Possible Solutions
The following simultaneous contradictory settings have occurred:
• b5-15 is not set to 0.0 (PID Sleep Function Operation Level)
• The stopping method is set to either DC Injection Braking or coast to stop
with a timer (b1-03 = 2 or 3).
• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
b5-01 is set to 1 or 2, enabling PID control, but the lower limit for the
frequency reference (d2-02) is not set to 0 while reverse output is enabled
(b5-11 = 1).
Correct the parameter settings.
b5-01 is set to 3 or 4, enabling PID control, but the lower limit for the
frequency reference (d2-01) is not 0.
Correct the parameter settings.
Digital Operator Display
Error Name
oPE10
V/f Data Setting Error
One of the following setting errors has occurred:
• E1-04
≥
E1-06
E1-06
≥
E1-07
E1-07
≥
E1-09
or E1-09
≥
E1-11
• E3-04
≥
E3-06
E3-06
≥
E3-07
E3-07
≥
E3-09
or E3-09
≥
E3-11
Cause
Possible Solutions
V/f pattern setting error.
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.
For motor 2, correct E3-04, E3-06, E3-07, E3-09, and E3-11.
2.6 Operator Programming Errors