E1-07
Middle Output Frequency
−
−
u
Setting 2: Conveyor Application
Table 4.7 Conveyor: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Drive Duty Selection
0: Heavy Duty
L3-04
Stall Prevention Selection during Deceleration
1: Enabled
Table 4.8 Conveyor: User Parameters (A2-01 to A2-16)
No.
Parameter Name
No.
Parameter Name
A1-02
Control Method Selection
C1-02
Deceleration Time 1
b1-01
Frequency Reference Selection 1
E2-01
Motor Rated Current
b1-02
Run Command Selection 1
L3-04
Stall Prevention Selection during Deceleration
C1-01
Acceleration Time 1
−
−
u
Setting 3: Exhaust Fan Application
Table 4.9 Exhaust Fan: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C6-01
Drive Duty Selection
1: Normal Duty
E1-03
V/f Pattern Selection
0FH
E1-07
Middle Output Frequency
30.0 Hz
E1-08
Middle Output Frequency Voltage
50.0 V
L2-01
Momentary Power Loss Operation Selection
1: Enabled
L3-04
Stall Prevention Selection during Deceleration
1: Enabled
Table 4.10 Exhaust Fan: User Parameters (A2-01 to A2-16)
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
E1-07
Middle Output Frequency
b1-02
Run Command Selection 1
E1-08
Middle Output Frequency Voltage
b1-04
Reverse Operation Selection
E2-01
Motor Rated Current
b3-01
Speed Search Selection at Start
H1-05
Multi-Function Digital Input Terminal S5 Function
Selection
C1-01
Acceleration Time 1
H1-06
Multi-Function Digital Input Terminal S6 Function
Selection
C1-02
Deceleration Time 1
H1-07
Multi-Function Digital Input Terminal S7 Function
Selection
E1-03
V/f Pattern Selection
L5-01
Number of Auto Restart Attempts
u
Setting 4: HVAC Fan Application
Table 4.11 HVAC Fan: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
4.6 Application Selection