No.
Name
Description
Analog Output
Level
Unit
Control
Mode
Addr.
Hex
V/
f
O
L
V
P
M
U5-01
PID Feedback
Displays the PID feedback value in.
10 V: 100%
(max. freq.)
0.01
%
A A A
57
U5-02
PID Input
Displays the amount of PID input (deviation between PID
target and feedback).
0.01
%
A A A
63
U5-03
PID Output
Displays PID control output.
0.01
%
A A A
64
U5-04
PID Setpoint
Displays the PID setpoint.
0.01
%
A A A
65
U5-05
PID Differential Feedback
Displays the 2nd PID feedback value if differential feedback
is used.
0.01
%
A A A
7D2
U5-06
PID Adjusted Feedback
Displays the difference of both feedback values if differential
feedback is used (U5-01) - (U5-05).
If differential feedback is not used, then U5-01 and U5-06
will be the same.
0.01
%
A A A
7D3
U6: Control Monitor
Use U6 monitors to display drive control information.
U6-01
Motor Secondary Current (Iq) Displays the value of the motor secondary current (Iq).
10 V: 100%
0.1% A A A
51
U6-02
Motor Excitation Current (ld) Displays the value calculated for the motor excitation current
(Id).
10 V: 100%
0.1% − A A
52
U6-03
ASR Input
Displays the ASR input value if V/f Control with Simple PG
Feedback is enabled.
10 V: 100%
(max. freq.)
0.1% A −
−
54
U6-04
ASR Output
Displays the ASR output value if V/f Control with Simple
PG Feedback is enabled.
10 V: 100%
(max. freq.)
0.1% A −
−
55
U6-05
Output voltage reference (Vq) Output voltage reference (Vq). (q-axis)
10 V: 200 V
(400 V)
0.1
Vac
− A A
59
U6-06
Output Voltage Reference
(Vd)
Output voltage reference (Vd). (d-axis)
10 V: 200 V
(400 V)
0.1
Vac
− A A
5A
U6-07
q-axis ACR Output
Displays the current control (ACR) output of for the motor
secondary current (Iq).
10 V: 100%
0.1% − A −
5F
U6-08
d-Axis ACR Output
Displays the current control (ACR) output of for the motor
excitation current (Id).
10 V: 100%
0.1% − A −
60
U6-20
Frequency Reference Bias
(Up/Down 2)
Displays the bias value used to adjust the frequency
reference.
10 V: max.
frequency
0.1% A A A
7D4
U6-21
Offset Frequency
The total value of the offset frequencies d7-01, d7-02 and
d7-03 selected with digital inputs 44 to 46 is displayed.
10 V: max.
frequency
0.1% A A A
7D5
U6-80 to
U6-99
Option Monitors 1 to 20
Monitors reserved for use by the communication option card.
Monitor content varies based on the communication option
connected to the drive.
Refer to the instruction manual for the option card for more
information..
No signal output
avail.
–
A A A 7B0 to
7F9
U8: Custom Monitors for DriveWorksEZ
U8 monitors are reserved for DriveWorksEZ
U8-01
–
Reserved for DriveWorksEZ, Monitor 1.
–
0.01
%
Α A Α
1950
U8-02
–
Reserved for DriveWorksEZ, Monitor 2.
–
0.01
%
A A A
1951
U8-03
–
Reserved for DriveWorksEZ, Monitor 3.
–
0.01
%
A A A
1952
U8-04
–
Reserved for DriveWorksEZ, Monitor 4.
–
0.01
%
A A A
1953
U8-05
–
Reserved for DriveWorksEZ, Monitor 5.
–
0.01
%
A A A
1954
U8-06
–
Reserved for DriveWorksEZ, Monitor 6.
–
0.01
%
A A A
1955
U8-07
–
Reserved for DriveWorksEZ, Monitor 7.
–
0.01
%
A A A
1956
B.2 Parameter Table
404