H3 Multi-Function Analog Input Settings
H3-
oo
Setting
Function
Maximum Input Level Possible
Control
Mode
Pg.
V/
f
O
L
V
P
M
C
PID Set Point
10 V = 100%
O
O
O
E
Motor Temperature (PTC input)
10 V = 100.00%
O
O
O
F
Not used/Through Mode
–
O
O
O
10
FWD Torque Limit
Motor rated torque
−
O
−
11
REV Torque Limit
Motor rated torque
−
O
−
12
Regenerative Torque Limit
Motor rated torque
−
O
−
15
FWD/REV Torque Limit
Motor rated torque
−
O
−
16
Differential PID Feedback
10 V = 100%
O
O
O
30/31
DWEZ Analog Input 1/2
Depending on function.
O
O
O
41
<1>
Output Voltage Gain
10 V = 100%
O
−
−
<1> Parameter available in drive software versions PRG: 1016 and later.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
H4-01
Multi-Function Analog
Output Terminal AM
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
U
o
-
oo
. For example, enter “103” for U1-03.
When using this terminal in through mode or when not using
it at all, set “000” or “031”.
000 to 999
<1>
102
A A A
41D
H4-02
<2>
Multi-Function Analog
Output Terminal AM Gain
Sets terminal AM output gain.
Maximum output voltage is 10 V.
-999.9 to
999.9
100.0
%
S
S
S
41E
H4-03
<2>
Multi-Function Analog
Output Terminal AM Bias
Sets terminal AM output bias.
-999.9 to
999.9
0.0% A A A
41F
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.
H5-01
<3>
Drive Node Address
Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
to take effect.
0 to 20 H
1F
A A A
425
H5-02
Communication Speed
Selection
Selects the baud rate for MEMOBUS/Modbus terminals R+,
R-, S+ and S-. Cycle power for the setting to take effect.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19200 bps
5 : 38400 bps
6 : 57600 bps
7 : 76800 bps
8 : 115200 bps
0 to 8
3
A A A
426
H5-03
Communication Parity
Selection
Selects the communication parity for MEMOBUS/Modbus
terminals R+, R-, S+ and S-. Cycle power for the setting to
take effect.
0: No parity
1: Even parity
2: Odd parity
0 to 2
0
A A A
427
B.2 Parameter Table
382
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual