No.
Name
Description
Range
Def.
Control
Mode
Addr. Hex Pg.
V/f O
LV PM
E3-04
Motor 2 Max Output
Frequency
To set linear V/f characteristics, set the same values for
E3-07 and E3-09. In this case, the setting for E3-08 will be
disregarded.
Ensure that the five frequencies are set according to these
rules to prevent triggering an oPE10 fault:
E3-09 ≤ E3-07 < E3-06 ≤ Ε3−11 ≤ E3-04
Note:
Setting E3-11 to 0 disables both E3-11 and E3-12, and
the above conditions do not apply.
E3-09 E3-07 E3-06 E3-11 E3-04
E3-05
E3-12
E3-13
E3-08
E3-10
VACrms Out (V)
Frequency (Hz)
40.0 to
400.0
60 Hz
A
A
−
31A
E3-05
<1>
Motor 2 Max
Voltage
0.0 to 255.0 230.0 V
A
A
−
31B
E3-06
Motor 2 Base
Frequency
0.0 to
E3-04
60 Hz
A
A
−
31C
E3-07
Motor 2 Mid Output
Freq.
0.0 to
E3-04
3.0 Hz
<12>
A
A
−
31D
E3-08
<1>
Motor 2 Mid Output
Freq. Voltage
0.0 to 255.0
18.4 V
<6>
<12>
A
A
−
31E
E3-09
Motor 2 Min. Output
Freq.
0.0 to
E3-04
1.5 Hz
<12>
A
A
−
31F
E3-10
<1>
Motor 2 Min. Output
Freq. Voltage
0.0 to 255.0
13.8 V
<6>
<12>
A
A
−
320
E3-11
<7>
Motor 2 Mid Output
Frequency 2
0.0 to
E3-04
0.0 Hz
A
A
−
345
E3-12
<1>
<13>
Motor 2 Mid Output
Frequency Voltage
2
0.0 to 255.0
<1>
0.0 Vac
A
A
−
346
E3-13
<1>
<9>
Motor 2 Base
Voltage
0.0 to 255.0
<1>
0.0 Vac
A
S
−
347
E4: Motor 2 Parameters
Use E4 parameters to control a second motor operating on the same drive.
E4-01
Motor 2 Rated
Current
Sets the motor 2 nameplate full load current in amperes (A).
This value is automatically set during Auto-Tuning.
10 to 200%
of drive
rated
current
<10>
A
A
−
321
E4-02
Motor 2 Rated Slip
Sets the motor 2 rated slip in Hz. Automatically set during
Auto-Tuning.
0.00 to
20.00
<10>
A
A
−
322
E4-03
Motor 2 Rated No-
Load Current
Sets the magnetizing current of motor 2 in Ampere.
Automatically set during Rotational Auto-Tuning.
0 to less
than E4-01
<9>
<10>
A
A
−
323
E4-04
Motor 2 Motor Poles Sets the number of poles of motor 2. This value is
automatically set during Auto-Tuning.
2 to 48
4 poles
A
A
−
324
E4-05
Motor 2 Line-to-
Line Resistance
Sets the phase-to-phase resistance of motor 2 in ohms.
Automatically during Auto-Tuning.
0.000 to
65.000
<11>
<10>
A
A
−
325
E4-06
Motor 2 Leakage
Inductance
Sets the voltage drop due to motor leakage inductance as a
percentage of rated voltage of motor 2. Automatically set
during Auto-Tuning.
0.0 to 40.0
<10>
A
A
−
326
E4-07
Motor 2 Motor Iron-
Core Saturation
Coefficient 1
Set to the motor iron saturation coefficient at 50% of
magnetic flux. Automatically set during Rotational
Auto-Tuning.
0.00 to 0.50
0.50
−
A
−
343
E4-08
Motor 2 Motor Iron-
Core Saturation
Coefficient 2
Set to the motor iron saturation coefficient at 75% of
magnetic flux. This value is automatically set during
Rotational Auto-Tuning.
Setting for
E4-07 to
0.75
0.75
−
A
−
344
E4-09
Motor 2 Mechanical
Loss
Sets the motor mechanical loss as a percentage of motor rated
power (kW) capacity.
Adjust in the following circumstances:
• When there is a large amount of torque loss due to motor
bearing friction.
• When there is a large amount of torque loss.
0.00 to 10.0
0.0
−
A
−
33F
E4-10
Motor 2 Iron Loss
Sets the motor iron loss in watts.
0 to 65535
<10>
Α
−
−
340
E4-11
Motor 2 Rated
Capacity
Sets the motor rated capacity in kW. Automatically set
during Auto-Tuning.
0.00 to
650.00
<6>
A
A
−
327
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
369
B
Parameter List