No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
b1-03
Stopping Method Selection
Selects the stopping method when the run command is
removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection Braking to Stop
3: Coast with Timer
(A new run command is ignored if received before the timer
expires)
0 to 3
0
S
S
S
182
DC Injection Braking at Stop cannot be
selected when using Open Loop Vector for PM
motors.
b1-04
Reverse Operation Selection
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
0, 1
0
A A A
183
b1-07
LOCAL/REMOTE Run
Selection
Determines the operation when the Run command source is
switched from LOCAL to REMOTE or between Run source 1
and 2 while an external Run command is active at the new
source.
0: External Run command has to be cycled at the new source
to be activated.
1: External Run command at new source is accepted
immediately.
0, 1
0
A A A
186
b1-08
Run Command Selection
while in Programming Mode
0: Run command accepted only in the operation menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during Run
0 to 2
0
A A A
187
b1-14
Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2 and
W/T3.
0 : Standard
1 : Switch phase order
0, 1
0
A A A
1C3
b1-15
Frequency Reference
Selection 2
Selects the frequency reference input source 2.
0: Operator - Digital preset speed d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4
0
A A A
1C4
b1-16
Run Command Selection 2
Selects the run command input source 2.
0: Operator - RUN and STOP keys on the digital operator.
1: Digital input terminals
2: MEMOBUS communications
3: Option PCB
0 to 3
0
A A A
1C5
b1-17
Run Command at Power Up
Determines the operation when a Run command is active at
power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
0, 1
0
A A A
1C6
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
b2-01
DC Injection Braking Start
Frequency
Sets the frequency at which DC Injection Braking starts when
Ramp to Stop (b1-03 = 0) is selected. If b2-01< E1-09, DC
Injection Braking starts at E1-09.
0.0 to 10.0 0.5
Hz
A A A
189
b2-02
DC Injection Braking Current Sets the DC Injection Braking current as a percentage of the
drive rated current.
0 to 75
50% A A A
18A
b2-03
DC Injection Braking Time/
DC Excitation Time at Start
Sets DC Injection Braking time at start. Disabled when set to
0.00 seconds.
0.00 to
10.00
0.00 s
<1>
A A A
18B
b2-04
DC Injection Braking Time at
Stop
Sets DC Injection Braking time at stop.
When b1-03 = 2, actual DC Injection time is calculated as
follows:
(b2-04) x 10 x (Output Freq)/(E1-04). When b1-03 = 0, this
parameter sets the amount of DC Injection time applied to the
motor at the end of the decel ramp or High Slip Braking.
Disabled when set to 0.00.
0.00 to
10.00
0.50 s A A −
18C
b2-08
Magnetic Flux Compensation
Value
Sets the magnetic flux compensation as a percentage of the no-
load current value (E2-03).
0 to 1000
0%
− A −
190
b2-12
Short Circuit Brake Time at
Start
Sets the time for Short-Circuit brake operation at start.
Disabled when set to 0.00.
<2>
0.00 to
25.50
0.00 s −
− A
1BA
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
357
B
Parameter List