No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
A1-06 Application Preset
Sets parameters that are commonly used in certain applications to
A2-01 through A2-16 for easier access.
0: General-purpose (A2 parameters are not affected)
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
8: Conveyor 2
<4>
Note:
Application Preset settings 6 and 7 are only present in
drive software versions PRG: 1011 and earlier.
0 to 5; 8
0
A A A
127
A1-07
<2>
DriveWorksEZ
Function Selection
0: Disabled
1: Enabled
2: Multi-function input (enabled when H1-
oo
= 9F)
0 to 2
0
A A A
128
A2: User Parameters
Use A2 parameters to program the drive.
A2-01
to
A2-32
User Parameters, 1 to 32 Parameters that were recently edited are listed here. The user can
also select parameters to appear here for quick access. Parameters
will be stored here for quick access when A1-01 = 1.
A1-00 to
o2-08
<3>
A A A
106 to
125
A2-33 User Parameter
Automatic Selection
0: Parameters A2-01 through A2-32 are reserved for the user to
create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited
parameters will be saved to A2-17 through A2-32 for quick access.
0, 1
<5>
A A A
126
<1> Parameter can be changed during run.
<2> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<3> Default setting value is dependent on parameter A1-06, Application Selection.
<4> Available in drive software versions PRG: 1020 and later.
<5> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06
≠
0.
u
b: Application
Application parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID
control, the Dwell function, Energy Savings and a variety of other application-related settings.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01
Frequency Reference
Selection 1
Selects the frequency reference input source.
0: Digital operator - Digital preset speed d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2.
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4
1
S
S
S
180
b1-02
Run Command Selection 1
Selects the run command input source.
0: Digital operator - RUN and STOP keys on the digital
operator.
1: Digital input terminals
2: MEMOBUS communications
3: Option PCB.
0 to 3
1
S
S
S
181
B.2 Parameter Table
356