Figure 5.91 Ready to Set Frequency Reference
n
o2-06: Operation Selection when Digital LCD Operator is Disconnected
Determines if the drive will stop when an external LCD operator is removed in LOCAL mode or with b1-02 set to 0.
Note:
An LCD operator is available as an option. This setting is not applicable to the standard LED operator that comes with the drive.
No.
Name
Setting Range
Default
o2-06
Digital Operator Disconnection Operation
0 or 1
0
Setting 0: Continue Operation
The operation is continued.
Setting 1: Trigger a Fault
The operation is stopped and an oPr fault is triggered. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up when the Run command is set to be given from
the digital operator.
Note:
This parameter is effective only when the Run command is set to be given from the digital operator (b1-02/16 = 0).
No.
Name
Setting Range
Default
o2-07
Motor Direction at Power Up when Using Operator
0 or 1
0
Setting 0: Forward
Setting 1: Reverse
u
o3: Copy Function
Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive.
n
o3-01: Copy Function Selection
This parameter controls the copying of parameters to and from the LED operator (option). The copy function will change
certain parameter default settings depending on the regional specification of the drive.
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
0: COPY SELECT (no function)
1: INV --> OP READ
All parameters are copied from the drive to the digital operator.
Note:
Set o3-02 to 1 to unlock copy protection.
2: OP --> INV WRITE
All parameters are copied from the digital operator to the drive.
3: OP<-->INV VERIFY
Parameter settings in the drive are compared to those in the digital operator.
Note:
When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur.
n
o3-02 Copy Allowed Selection
Enables and disables the digital operator copy functions.
5.10 o: Operator Related Settings
250